E6581222

60

9. Parameter data

Explanation of parameters for VF-S11 series is described here. For communication purposes, see
the parameter list on inverter's instruction manual regarding the communication number, adjustment
range and so forth.

■ Referring to the parameter list

Title

Com-

munica-

tion No.

Function

unit

Minimum

setting unit

Panel/Com

munication

Adjustment range

Default

setting

User

setting

Reference

auh

-

History function

-

-

Displays parameters in
groups of five in the reverse
order to that in which their
settings were changed.
* (Possible to edit)

-

4.1.4



0000

Automatic ac-

celera-

tion/deceleration

-

-

0: Disabled (manual)
1: Automatic
2:Automatic (only at accelera-

tion)

0

5.1.1



0001

Automatic tor-

que boost

-

-

0:Disabled
1:Automatic torque boost +

autotuning

2:Vector control + auto-tuning

3:Energy saving + auto-tuning

0

5.2



0009

Acceleration
time1

S

0.1/0.1

0.0-3200

10.0

5.1.2

- The summary of parameter list relating to the communication is as follows.

(1) “Title” means the display on the inverter panel.

(2) “Communication number” is affixed to each parameter that is necessary for designating the parameter for com-

munication.

(3) "Adjustment range" means a data range adjustable for a parameter, and the data cannot be written outside the

range. The data have been expressed in the decimal notation. For writing the data through the communication
function, take the minimum setting unit into consideration, and use hexadecimal system.

(4) "Minimum setup unit" is the unit of a single data (when the minimum unit is "-", 1 is equal to 1).

For example, the "minimum setup unit" of acceleration time () is 0.01, and 1 is equal to 0.01s. For setting a
data to 10 seconds, transmit 03E8h [10 0.01=1000d=03E8h] by communication.