beautypg.com

Alarm, Monitor (fc91), Information – Toshiba TOSVERT VF-S11 User Manual

Page 52: Cumulative operation time alarm monitor (fe79)

background image

E6581222

50

„

Alarm

information

monitor (FC91)

Bit

Specifications

0

1

Remarks

(Code displayed on the panel)

0

Over-current alarm

Normal

Alarming



flickering

1

Inverter overload alarm

Normal

Alarming



flickering

2

Motor overload alarm

Normal

Alarming



flickering

3

Overheat alarm

Normal

Alarming



flickering

4

Overvoltage alarm

Normal

Alarming



flickering

5

Main circuit undervoltage alarm

Normal

Alarming

-

6

(Reserved)

-

-

-

7

Low current alarm

Normal

Alarming

-

8

Over-torque alarm

Normal

Alarming

-

9

Braking resistor overload alarm

Normal

Alarming

-

10

Cumulative operation hours
alarm

Normal

Alarming

-

11

(Reserved)

-

-

-

12

(Reserved)

-

-

-

13

Main-circuit voltage error alarm

Normal

Alarming

“ flickering

14

At the time of the instant black-
out, Forced deceleration/stop

-

Decelerating,
stopping

Related: F256 setting

15

An automatic stop during the
lower limit frequency continu-
ance

-

Decelerating,
stopping

Related: F302 setting

„

Cumulative operation time alarm monitor (FE79)

Bit

Specifications

0

1

Remarks

0

Fan life alarm

Normal

Alarm issued

-

1

Circuit board life alarm

Normal

Alarm issued

-

2

Main-circuit capacitor life alarm

Normal

Alarm issued

-

3

User set alarm

Normal

Alarm issued

-

4-15 (Reserved)

-

-

-