beautypg.com

Frequency setting from the computer, Communication command3 – Toshiba TOSVERT VF-S11 User Manual

Page 48

background image

E6581222

46

„

Communication command3

(Communication number: FA26)

The RY Terminal Output Hold Command and OUT Terminal Output Hold Command are always en-

abled even though communication command priority is not set.

Table 3 Data construction of Serial Communication Command 3 (FA26)

Bit

Function

0

1

Remarks

0

RY terminal output hold

OFF

Once it is turned
on, a RY terminal
holds that condi-
tion.

Always enabled even if
communication command
is not enabled

1

OUT terminal output hold

OFF

Once it is turned
on, an OUT ter-
minal holds that
condition.

Always enabled even if
communication command
is not enabled

2

(Reserved)

3

(Reserved)

4

(Reserved)

5

(Reserved)

6

(Reserved)

7

(Reserved)

8

(Reserved)

9

(Reserved)

10

(Reserved)

11

(Reserved)

12

(Reserved)

13

(Reserved)

14

(Reserved)

15

(Reserved)

„

Frequency setting from the computer

(communication number: FA01)

Setting range: 0 to Maximum frequency ()
This frequency command is enabled only when the frequency command by communication is en-

abled by setting “serial communication (“3” for Communication Number FA04) by the speed com-
mand selection parameter () or setting command priority (Bit 14 of Communication Number
FA00 to “1” (enable)) by the communication command. In this case, frequency commands by
communication will be enabled independent of  setting. However, enabled commands and
frequencies are given the priority if “48: Forced change from communication to local,” “52: Forced
operation,” or “53: Fire speed” is set by input terminal function selection ( to ).

Once enabled, this frequency setting will be enabled till disable is set (0 setting), power is turned off

or is reset, or standard shipment setting () is selected.

Set a frequency by communication hexadecimal in Communication Number FA01. (1 = 0.01Hz
(unit))

Example: Operation frequency 80Hz command (PFA011F40) CR
80Hz = 80 ÷ 0.01 = 8000 = 1F40H