beautypg.com

Trip code monitor, Fc90, Fe10 to fe13) – Toshiba TOSVERT VF-S11 User Manual

Page 53

background image

E6581222

51

„

Trip code monitor (

current status:

FC90:

historic records:

FE10 to FE13)

Code

Data

(hexadeci-

mal number)

Data

(decimal
number)

Description

nerr

0

0 No error

oc1

1

1 Over-current during acceleration

oc2

2

2 Over-current during deceleration

oc3

3

3 Over-current during constant speed operation

ocl

4

4 Over-current in load at startup

oca

5

5 Short circuit in arm

ephi

8

8 Input phase failure

epho

9

9 Output phase failure

op1

A

10 Overvoltage during acceleration

op2

B

11 Overvoltage during deceleration

op3

C

12 Overvoltage during constant speed operation

ol1

D

13 Over-LOAD in inverter

ol2

E

14 Over-LOAD in motor

oh

10

16 Overheat trip

e

11

17 Emergency stop

eep1

12

18 EEPROM fault 1 (writing error)

eep2

13

19 EEPROM fault 2 (reading error)

eep3

14

20 EEPROM fault 3 (internal fault)

err2

15

21 RAM fault

err3

16

22 ROM fault

err4

17

23 CPU fault

err5

18

24 Communication error trip

err7

1A

26 Current detector fault

err8

1B

27 Optional circuit board type error

uc

1D

29 Small-current trip

up1

1E

30 Trip due to undervoltage in main circuit

ot

20

32 Over-torque trip

ef2

22

34 Ground fault trip (hardware detection)

oc1p

25

37 Overcurrent flowing in element during acceleration

oc2p

26

38 Overcurrent flowing in element during deceleration

oc3p

27

39 Overcurrent flowing in element during operation

etyp

29

41 Inverter type error

oh2

2E

46 External thermal input

sout

2F 47

PM motor step-out

e-18

32 50 VIA cable break in an analog signal cable

e-19

33

51 CPU fault

e-20

34

52 Excess torque boost

e-21

35

53 CPU fault

etn1

54

84 Auto-tuning error