Trip code monitor, Fc90, Fe10 to fe13) – Toshiba TOSVERT VF-S11 User Manual
Page 53
E6581222
51
Trip code monitor (
current status:
FC90:
historic records:
FE10 to FE13)
Code
Data
(hexadeci-
mal number)
Data
(decimal
number)
Description
nerr
0
0 No error
oc1
1
1 Over-current during acceleration
oc2
2
2 Over-current during deceleration
oc3
3
3 Over-current during constant speed operation
ocl
4
4 Over-current in load at startup
oca
5
5 Short circuit in arm
ephi
8
8 Input phase failure
epho
9
9 Output phase failure
op1
A
10 Overvoltage during acceleration
op2
B
11 Overvoltage during deceleration
op3
C
12 Overvoltage during constant speed operation
ol1
D
13 Over-LOAD in inverter
ol2
E
14 Over-LOAD in motor
oh
10
16 Overheat trip
e
11
17 Emergency stop
eep1
12
18 EEPROM fault 1 (writing error)
eep2
13
19 EEPROM fault 2 (reading error)
eep3
14
20 EEPROM fault 3 (internal fault)
err2
15
21 RAM fault
err3
16
22 ROM fault
err4
17
23 CPU fault
err5
18
24 Communication error trip
err7
1A
26 Current detector fault
err8
1B
27 Optional circuit board type error
uc
1D
29 Small-current trip
up1
1E
30 Trip due to undervoltage in main circuit
ot
20
32 Over-torque trip
ef2
22
34 Ground fault trip (hardware detection)
oc1p
25
37 Overcurrent flowing in element during acceleration
oc2p
26
38 Overcurrent flowing in element during deceleration
oc3p
27
39 Overcurrent flowing in element during operation
etyp
29
41 Inverter type error
oh2
2E
46 External thermal input
sout
2F 47
PM motor step-out
e-18
32 50 VIA cable break in an analog signal cable
e-19
33
51 CPU fault
e-20
34
52 Excess torque boost
e-21
35
53 CPU fault
etn1
54
84 Auto-tuning error