beautypg.com

TDK GENESYS 750W HALF RACK User Manual

Page 39

background image

83-507-5002 Rev. B

31

Table 4-3: SW1 Positions Functions

Position

Function

DOWN (Factory default)

UP

SW1-1

Output Voltage

remote analog programming

Output Voltage

programmed by

Front Panel

Output Voltage

programmed by remote

analog voltage

SW1-2

Output Current

remote analog programming

Output Current

programmed by Front

Panel

Output Current

programmed by remote

analog voltage

SW1-3

Programming Range Select

(Remote voltage/resistive)

0-5V/(0-5Kohm)

0-10V/(0-10Kohm)

SW1-4

Output Voltage and

Current Monitoring Range

0-5V

0-10V

SW1-5

Shut-Off Logic select

Off: Low (0-0.6V) or Short
On: High (2-15V) or Open

Off: Low (2-15V) or Open

On: High (0-0.6V) or Short

SW1-6

RS232/485 select

RS232 interface

RS485 interface

SW1-7

Output Voltage

Resistive Programming

Output Voltage

programmed by Front

Panel

Output Voltage

programmed by

external resistor

SW1-8

Output Current

Resistive Programming

Output Current

programmed by Front

Panel

Output Current

programmed by external

resistor

SW1-9

Enable/Disable control

Rear panel

Enable/Disable control is

not Active

Rear panel

Enable/Disable control

is Active


4.4.2 Resetting the SW1 switch
Before making any changes to the SW1 switch setting, disable the power supply output by press-
ing the front panel OUT button. Ensure that the Output Voltage falls to zero and the OUT LED is
Off. Then use any small flat-bladed screwdriver to change the SW1 switch setting.

4.5 REAR PANEL J1 PROGRAMMING AND MONITORING CONNECTOR

The J1 Programming and Monitoring connector is a DB25 subminiature connector located on the
power supply rear panel. Refer to Table 4-4 for description of the connector functions. The power
supply default configuration is Local operation, which does not require connections to J1. For
remote operation using J1 signals, use the plug provided with power supply (or equivalent type).
It is essential to use a plastic body plug to conform to Safety Agency requirements. If a shield is
required for the J1 wires, connect the shield to a power supply chassis ground screw.

4.5.1 Making J1 connections

-J1 Connector type: AMP, P/N:747461-3

-J1 plug description: AMP, P/N:745211-2

-Wire dimension range: AWG26-22
-Manual Pistol grip tool:

Handle:AMP, P/N:58074-1

Head:AMP, P/N:58063-2

-Insertion/Extraction tool: AMP, 91232-1

Before making any connection, turn the AC On/Off switch to the Off position and wait until the
front panel display has turned Off.