38 N OMWT-SOFT-OPC Server Tags
OMWT-SOFT-OPC Server
AnalogInput: AIn
(OMWT-AIN5V, OMWT-AIN10V, OMWT-AIN20MA, OMWT-VIB, OMWT-
MOT)
online(R) - indicates if the device is communicating (0 or 1)
polltime(R/W) - how often to poll the device (in milliseconds)
nodaladdress (R) – (TCP/IP Receiver). The node address starts at 1. For
TCP/IP Receivers, the node address corresponds to the node number
for the TCP/IP connection.
repeateraddress (R) – (Wireless mode) contains the location identifier of
the OMWT-REPEAT repeater. If the sensor did not pass through a
repeater then the value is 0.
serialno(R) - registration number of the sensor
input(R) - current value of the sensor as percent of full scale
input.conv(R/W) - unit conversion parameters string.
(Cal1Raw,Cal1Engr,Cal2Raw,Cal2Engr)
input.units(R/W) – default is '%'.
input.desc(R/W) - General identification description field.
(R) – indicates that the tag is readable.
(R/W) – indicates that the tag is both readable and writeable. OPC Write operations
will either change an I/O point at the device, or an operation will be performed.