24 N OMWT-SOFT-OPC Server .ini File Format
OMWT-SOFT-OPC Server
Analog Input
(OMWT-AIN5V, OMWT-AIN10V, OMWT-AIN20MA, OMWT-VIB, OMWT-
MOT)
[Devicen]
- Section name
Address – serial number of the sensor.
DeviceType - DeviceType=AI
PollTime - How often to poll the device (ms).
Label - Name used for the device (and Topic) (typically AI1)
Log - Enable/disable logging of device.
LogDecimalPlaces - Number of decimals to create when logging.
Cal1Raw - Two point calibration point 1 (default 0).
Cal2Raw - Two point calibration point 2 (default 4095).
Cal1Engr - Two point calibration engineering units for point 1 (default 0).
Cal2Engr - Two point calibration engineering units for point 2 (default 10).
DeadBand - Dead band filtering value in % of full scale (Cal2Engr).
FilterElements – running macro filter of the sampled data. Syntax: [no. of
elements, type] where no. of elements is number of samples to filter;
type – “AVERAGE”, “MEDIAN” and “AVERAGEMEDIAN”.
Default is “=1,MEDIAN” – no filtering. Example:
FilterElements=3,AVERAGE
Units - units label (default "%").
Description - Generic description field
CorrID – What CorrectionID to use with this device. Must be found in the
"Correction.INI" file that you write and keep in the same directory as
the OMWT-SOFT-OPC.ini file. 0 is the default and means no
correction; 127 is the maximum.