beautypg.com

Cnttemp: cnttempn, Alarmtemp: alarmtempn – Omega Engineering M-4066 User Manual

Page 41

background image

OMWT-SOFT-OPC Server

OMWT-SOFT-OPC Server Tags N 37

ALARMTEMP: ALARMTEMPn

(OMWT-TEMPALRM)

online (R) - indicates if the device is communicating (0 or 1)
nodaladdress (R) – (TCP/IP Receiver). The node address starts at 1. For

TCP/IP Receivers, the node address corresponds to the node number

for the TCP/IP connection.

repeateraddress (R) – (Wireless mode) contains the location identifier of

the OMWT-REPEAT repeater. If the sensor did not pass through a

repeater then the value is 0.

polltime (R/W) - how often to poll the device (in milliseconds)
serialno (R) - registration number of the temperature sensor
input (R) - current temperature in engineering units
input.raw (R) - current temperature in ºC
input.units (R/W) -engineering units of the input tag (ºC, ºF, or ºK). When

this tag is written, it changes the temperature scale in the input.value

tag. input.units must be one of the following: "Celsius",”C”,

"Fahrenheit",”F”, or "Kelvin",”K”.

input.deadband (R/W) - filtering deadband in ºC
input.conv (R/W) - calibration and unit conversion parameters string.

(Cal1Raw,Cal1Engr,Cal2Raw,Cal2Engr)

input.desc (R) - General identification description field.
input.isalarm (R) – is the temperature above the set point (0 or 1).
input.isalarmtime (R) – has the temperature been above the set point for

more than the alarm time (0 or 1).

input.marker (R) – general purpose 8 bit identifier from the sensor
input.alarmtemp (R) – set point for the high temperature alarm in

engineering units

input.alarmtime (R) – set point for the amount of time that must pass for

the input to be above the input.alarmtemp to trigger the input.alarmtime

alarm

(R) – indicates that the tag is readable.
(R/W) – indicates that the tag is both readable and writeable. OPC Write operations

will either change an I/O point at the device, or an operation will be performed.