beautypg.com

Humidity, Cnttemp – Omega Engineering M-4066 User Manual

Page 25

background image

OMWT-SOFT-OPC Server

OMWT-SOFT-OPC Server .ini File Format N 21

CNTTEMP

(OMWT-DOORCNT)
[Devicen] - Section name.

Address – serial number of the sensor.
DeviceType - Device type. (DeviceType=CNTTEMP)
PollTime - How often to poll the device. (ms)
Label - Name used for the device (and Topic) (typically CNTTEMP1).
Log - Enable/disable logging of device.
LogDecimalPlaces - Number of decimals to create when logging.
Scale - Multiplier for Counter A
Units - Generic label for units - no function
Description - Generic description field
temp.Units - See OPC tag item temp.input.units for description.
temp.Cal1Raw - Two point calibration point 1.
temp.Cal2Raw - Two point calibration point 2.
temp.Cal1Engr - Two point calibration engineering units for point 1.
temp.Cal2Engr - Two point calibration engineering units for point 2.
temp.DeadBand - Dead band filtering value in ºC. (Default 0.00)
temp.FilterElements - running macro filter of the sampled data. Syntax:

[no. of elements, type] where no. of elements is number of samples to

filter; type – “AVERAGE”, “MEDIAN” and “AVERAGEMEDIAN”.

Default is “=0”. Example: FilterElements1=6,AVERAGE

temp.Description - General purpose description.
temp.CorrID – What CorrectionID to use with this device. Must be found

in the "Correction.INI" file that you write and keep in the same

directory as the OMWT-SOFT-OPC.ini file. 0 is the default and means

no correction; 127 is the maximum