18 N OMWT-SOFT-OPC Server .ini File Format

OMWT-SOFT-OPC Server

TEMPERATURE Setup

(OMWT-TEMP15 and OMWT-THERM)

[Devicen] - Section name.

Address - – serial number of the sensor.
DeviceType - Device type. (DeviceType=TEMP)
PollTime - How often to poll the device. (ms)
Label - Name used for the device (and Topic).
Log - Enable/disable logging of device.
LogDecimalPlaces - Number of decimals to create when logging.
Units - See OPC tags list under input.units for description.
Cal1Raw - Two point calibration point 1.
Cal2Raw - Two point calibration point 2.
Cal1Engr - Two point calibration engineering units for point 1.
Cal2Engr - Two point calibration engineering units for point 2.
DeadBand - Dead band filtering value in ºC. (Default 0.01)
FilterElements - running macro filter of the sampled data. Syntax: [no. of

elements, type] where no. of elements is number of samples to filter;

type – “AVERAGE”, “MEDIAN” and “AVERAGEMEDIAN”.

Default is “=3,MEDIAN”. Example: FilterElements1=6,AVERAGE

Description - General purpose description.
CorrID – What CorrectionID to use with this device. Must be found in the

"Correction.INI" file that you write and keep in the same directory as

the OMWT-SOFT-OPC.ini file. 0 is the default and means no

correction; 127 is the maximum. If the device type is a thermistor, the

default CorrID is found in the [Server] section

"DefaultThermistorCorrID", which defaults to 128.