11.3 Outside Combustion Air Supply
Where necessary, clean air may be ducted into the burner
box through an added spigot on the back of the burner
box replacing the existing dust arrest baffle plate.
See Page 50, Section 11.1.3 for recommendations on duct
length. Air duct should be as straight as possible. Do not
use bends in excess of 45°. Consult the manufacturer if
more than 2 x 45° offset bends are necessary. The fresh
air duct must be self supporting.
11.3.1 Air Supply Requirements
When fresh air duct is used, follow one of these rules:
• The flue must penetrate the roof while fresh air can
penetrate any wall. (
• The flue and fresh air supply must penetrate the
same roof, at a minimum of 1 m apart. (
• The flue must penetrate 1 m higher than the fresh air
inlet on the same wall. (
Fan Tube
Flue Pipe
Flue Adapter
Fan Assembly
Screw
(Torque: 2 Nm
18 in lb)
Lockwasher
Nut
Fan Tube
Fan
A
B
C
End of Tube
Heater Model
Fan Model
A
B
C
Part Number
BH 15-30
Torin DSF-133-42
79 mm
95 mm
45 mm
C2374B
BH 35-50
AO Smith JF1G
89 mm
102 mm
51 mm
90710000
- Double Linear U-Tube and Multi-Burner Gas Fired Heating Systems BH15ST BH20ST and Multi-Burner Gas Fired Heating Systems BH45UT/EF and Multi-Burner Gas Fired Heating Systems BH70DL/EF and Multi-Burner Gas Fired Heating Systems BH25ST/EF and Multi-Burner Gas Fired Heating Systems BH45ST/EF and Multi-Burner Gas Fired Heating Systems BH25UT/EF and Multi-Burner Gas Fired Heating Systems BH50UT/EF and Multi-Burner Gas Fired Heating Systems BH40ST/EF and Multi-Burner Gas Fired Heating Systems BH40DL and Multi-Burner Gas Fired Heating Systems BH60DL/EF and Multi-Burner Gas Fired Heating Systems BH30DL and Multi-Burner Gas Fired Heating Systems BH40UT/EF and Multi-Burner Gas Fired Heating Systems BH15UT and Multi-Burner Gas Fired Heating Systems BH30ST/EF and Multi-Burner Gas Fired Heating Systems BH50ST/EF BH55ST and Multi-Burner Gas Fired Heating Systems BH35ST/EF