Roberts Gorden Vacuum Assisted Linear User Manual
Page 24

B
LACKHEAT
®
I
NSTALLATION
O
PERATION
AND
S
ERVICE
M
ANUAL
18 of 74
Figure 22: Double Linear Layout Overview
Model
BH30DL
BH40DL
BH50DL/EF
BH60DL/EF
BH70DL/EF
Reflector Overlap (approx.)
700 mm
250 mm
250 mm
530 mm
530 mm
Tee Assembly
Burner
Reflector
Tube
Tube/Reflector
Hanger
Coupling
Assembly
Fan
Assembly
LEGEND
BH60DL/EF
BH70DL/EF
g
c
b
d
e
b
f
e
e
Repeated
Opposite
Side
BH40DL
BH50DL/EF
g
c
b
d
e
b
f
e
Repeated
Opposite
Side
BH30DL
g
c
b
d
e
b
f
Repeated
Opposite
Side
a = reflector width (not shown) - 365 mm
b = end cap to burner/fan - 50 mm
c = end cap to hanger - 50 mm
d = distance first hanger - 2290 mm
e = distance typical between hangers - 3050 mm
f = burner height - 366 mm
g = burner length - 291 mm
This manual is related to the following products:
- Double Linear U-Tube and Multi-Burner Gas Fired Heating Systems BH15ST BH20ST and Multi-Burner Gas Fired Heating Systems BH45UT/EF and Multi-Burner Gas Fired Heating Systems BH70DL/EF and Multi-Burner Gas Fired Heating Systems BH25ST/EF and Multi-Burner Gas Fired Heating Systems BH45ST/EF and Multi-Burner Gas Fired Heating Systems BH25UT/EF and Multi-Burner Gas Fired Heating Systems BH50UT/EF and Multi-Burner Gas Fired Heating Systems BH40ST/EF and Multi-Burner Gas Fired Heating Systems BH40DL and Multi-Burner Gas Fired Heating Systems BH60DL/EF and Multi-Burner Gas Fired Heating Systems BH30DL and Multi-Burner Gas Fired Heating Systems BH40UT/EF and Multi-Burner Gas Fired Heating Systems BH15UT and Multi-Burner Gas Fired Heating Systems BH30ST/EF and Multi-Burner Gas Fired Heating Systems BH50ST/EF BH55ST and Multi-Burner Gas Fired Heating Systems BH35ST/EF