INSTALLATION

A-9

A-9

EAGLE™ 10,000

STANDBY POWER CONNECTIONS

The EAGLE 10,000 is suitable for temporary, standby,

or emergency power using the engine manufacturer’s

recommended maintenance schedule.

The EAGLE 10,000 can be permanently installed as a

standby power unit for 240V-3 wire, single phase 38

ampere service.

(Connections must be made by a licensed electri-

cian who can determine how the 120/240V power

can be adapted to the particular installation and

comply with all applicable electrical codes.) The

following information can be used as a guide by

the electrician for most applications (refer also to

the connection diagram shown in

Figure A.1.)

------------------------------------------------------------------------

-

1. Install a double pole, double throw switch between

the power company meter and the premises

disconnect.

Switch rating must be the same or greater than

the customer’s premises disconnect and service

overcurrent protection.

2. Take necessary steps to assure load is limited to

the capacity of the EAGLE 10,000 by installing a

38 amp 240V double pole circuit breaker.

Maximum rated load for the 240V auxiliary is 38

amperes. Loading above 38 amperes will reduce

output voltage below the allowable -10% of rated

voltage which may damage appliances or other

motor-driven equipment.

3. Install a 50 amp 120/240V plug (NEMA type 14-50)

to the Double Pole Circuit Breaker using No. 8,

4 conductor cable of the desired length. (The

50 amp 120/240V plug is available in the

optional plug kit.)

4. Plug this cable into the 50 amp 120/240V

receptacle on the EAGLE 10,000 case front.

WARNING

AUXILIARY POWER WHILE WELDING

Simultaneous welding and power loads are permitted

by following Table II. The permissible currents shown

assume that current is being drawn from either the

120V or 240V supply (not both at the same time). Also,

the “Output Control” is set at “10” for maximum auxil-

iary power.

TABLE II

SIMULTANEOUS WELDING AND POWER

Output Selector

Permissible Power

Permissible Auxiliary

Setting

Watts (Unity Power

Current in Amperes

Factor)

@ 120V

*

-or- @ 240V

Max. Stick or Wire

Feed Setting

None

0

0

145 Stick Setting

3450

32

16

90 Stick Setting

6000

50

**

25

NO WELDING

9000

76

**

38

*

Each duplex receptacle is limited to 20 amps.

**

Not to exceed 40A per 120VAC branch circuit

when splitting the 240 VAC output.