Sanyo C4272R S/C User Manual
Page 79
79
RC
(WL)
7-17. Wiring System Diagram for Group Control
This diagram shows when several units (maximum of
8) are controlled by a signal receiving unit (main
unit). In this case, a signal receiving unit can be
connected at any indoor unit.
Wiring procedure
Wire according to the diagram at left:
Address setting is executed automatically when the
outdoor unit is turned on.
Each successive unit will respond at one-second
intervals following the order of the group address
when the remote controller is operated.
Group control using 2 signal receiving units
It does not matter which of the 2 signal receiving units
you set as the main controller.
When using multiple signal receiving units (up to 2
can be used), one is the main signal receiving
unit and the other is the sub-signal receiving unit.
To set up a sub-signal receiving unit, change its
remote control address connector (RCU. ADR)
located on its PCB from main to sub position
(main: when shipped from factory).
(sub)
1 2
Wire joint
Remote
controller
(main)
: Ground (earth)
Connection wiring
for group control
1 2
U1 U2
U1 U2
U1 U2
U1 U2
U1 U2
U1 U2
U1 U2
U1 U2
1 2
Outdoor unit
Indoor unit
No. 1
1 2
Outdoor unit
Indoor unit
No. 2
1 2
Outdoor unit
Indoor unit
No. 3
1 2
Outdoor unit
Indoor unit
No. 8
07-115 SSHP_II 5/7/07 4:00 PM Page 79