CAUTION

CAUTION

WARNING

1. This unit requires no additional refrig-

erant charge up to 100 ft. tubing length.
In case of more than 100 ft., additional
refrigerant charge is required. Refer to
Table 1-11.

2. In case of multi type installation,

indoor units should be installed within
the same room. If multi type indoor
units are installed in different rooms,
temperature control may develop prob-
lems because thermostat operation
must follow the thermostat condition of
1 indoor unit only (the main unit).

Always check the gas density

for the room in which the unit is

installed.

Pay special attention to any
location, such as a basement
or recessed area, etc. where
leaked refrigerant can collect,
since refrigerant gas is heav-
ier than air.

22

486

972

1,449

1,935

2,421

2,907

3,384

3,870

4,356

4,842

54

108

161

215

269

323

376

430

484

538

ft.

3

ft.

2

Total amount of refrigerant

Min. indoor floor area

(when the ceiling is 9 ft. high)

Min. indoor volume

44

66

88 lbs.

Range below the
density limit of
0.3 oz./ft.

3

(Countermeasures
not needed)

Range above the
density limit of
0.3 oz./ft.

3

(Countermeasures
needed)

Check of limit density
When installing an air conditioner in a room, it is neces-

sary to ensure that even if the refrigerant gas acciden-

tally escapes, its density does not exceed the limit level.

If the density might exceed the limit level, it is neces-

sary to set up an opening between it and the adjacent

room, or to install mechanical ventilation which is inter-

locked with the leak detector.

(Total refrigerant charged amount: oz.)

(Min indoor volume where the indoor unit is installed: ft.

3

)

< Limit density 0.3 (oz./ft.

3

)

The limit density of refrigerant which is used in this unit

is 0.3 oz./ft.

3

(ISO 5149).

The shipped outdoor unit comes charged with the

amount of refrigerant fixed for each type; so add it to

the amount that is charged at the field. (For the refriger-

ant charge amount at shipment, refer to the unit’s

nameplate.)

Minimum indoor volume & floor area relative to

the amount of refrigerant is roughly as given in

the following table.

07-115 SSHP_II 5/7/07 3:59 PM Page 15