6-5. Wiring System Diagram for Multiple Remote

Controllers

When Installing Multiple Remote Controllers

This multiple remote controller system is used for

operating the unit(s) at different positions. (A maximum

of 2 remote controllers can be installed.)

Setting method

To execute this control, make the setting according

to the following procedure.

(1) Of the 2 installed remote controllers, make 1 the

main remote controller (factory-shipped state).

(2) On the other remote controller, change the address

connector on the PCB from main to sub position.

In this state, it functions as a sub-remote controller.

Basic wiring diagram

CAUTION

Install wiring correctly
(incorrect wiring will damage
the equipment).

To operate 1 indoor unit with 2 remote controllers set

at different places.

6-6. How to Switch the Indoor Temperature Sensor

The indoor unit and the remote controller both contain

an indoor temperature sensor. The sensors on either

unit can be used but normally only the sensor set on

the indoor unit is used. However, use the following

procedure if you must use the sensor on the remote

controller.

(1) Press and hold the

+

+

buttons for

at least 4 seconds.

Note: The Unit No. first displayed is the main

indoor unit address for group control.

Note: Do not press the

button.

(2) Select CODE NO. 32 with the Temp. setting (

)

/

buttons.

(3) Change the set data from 0000 to 0001 with the

Timer (

)

/

buttons.

(4) Press the

button. (Setting is OK if the blinking

display changes to a lit up display.)

(5) This is the usual off condition. At this time,

(remote controller) appears on the LCD display.

*1

If using 2 remote controllers, either one (main or

sub-remote controller) can be used to make settings

but only the main unit functions as the remote

controller sensor.

*2

The remote controller sensor will not function during

group control unless the group address is set in the

main remote controller indoor unit.

*3

Do not use the remote controller switch for the

remote control sensor if the remote sensor is being

used jointly with the remote controller switch.

NOTE

Remote controller

Remote controller
address connector

RCU. ADR

Main

Sub

RCU check

Remote control cable

(wire it at the

installation site)

Remote control
cable terminal
board

1 2

Indoor unit

Earth

(sub)

(main)

1 2

(Option)

1 2