Sanyo C4272R S/C User Manual
Page 63
63
RC
(WD)
6-4. Wiring System Diagram for Group Control
This diagram shows when several units (maximum
of 8) are controlled by a remote controller (main
unit).
In this case, a remote controller can be connected
at any indoor unit.
■ Wiring procedure
Wire according to the diagram at right:
●
Address setting is executed automatically when
the outdoor unit is turned on.
■ Group control using 2 remote controllers
It does not matter which of the 2 remote controllers
you set as the main controller.
When using multiple remote controllers (up to 2 of
them can be used), one is the main remote
controller and the other is the sub-remote
controller.
●
To set up a sub-remote controller, change its
remote control address connector (RCU. ADR)
located on its PCB from main to sub position
(main: when shipped from factory).
(sub)
1 2
Wire joint
Remote
controller
(main)
: Ground (earth)
Connection wiring
for group control
1 2
U1 U2
U1 U2
U1 U2
U1 U2
U1 U2
U1 U2
U1 U2
U1 U2
1 2
Outdoor unit
Indoor unit
No. 1
1 2
Outdoor unit
Indoor unit
No. 2
1 2
Outdoor unit
Indoor unit
No. 3
1 2
Outdoor unit
Indoor unit
No. 8
U1 U2
U1 U2
1 2
: Ground (earth)
Outdoor unit
Indoor unit
No. 1
1 2
Remote
controller
Inter-unit
control
wiring
Wire joint
07-115 SSHP_II 5/7/07 4:00 PM Page 63