Reference diagram for air-discharge chamber (field supply)

C(H)2672R / 3072R / 3672R / 4272R with STK-DRV80U & DRE140A

Required space around outdoor unit

If the air discharge chamber is used, the space shown below must be secured around the outdoor unit.

If the unit is used without the required space, a protective device may activate, preventing the unit from operating.

(1) Single-unit installation

CAUTION

The top and both sides must remain open. If there are obstacles to the front and rear of

the outdoor unit, the obstacle at either the front or rear must be no taller than the height of

the outdoor unit.

(2) Multiple-unit installation

Installation in lateral rows

CAUTION

The front and top must remain open.

The obstacles must be no taller than the height of the outdoor unit.

CAUTION

The front and both sides must remain open.

Installation in front-rear rows

Installation with intakes facing outlets

Installation with intakes facing

intakes or outlets facing outlets

Min. 39-3/8

Min. 7-7/8

More than 15-3/4

More than 11-13/16

More than 11-13/16

More than 7-7/8

Unit: inch

Unit: inch

More than 78-3/4

More than 15-3/4

More than 59-1/16

Unit: inch