SBD TANK TYPE HEATERS

SERVICE HANDBOOK

Technical Training Department

Ashland City, TN ©2003

30

TROUBLESHOOTING THE EFFIKAL DAMPER (continued)


Condition:
Thermostat closed, damper is open fully

STEP 10A

TEST FOR 24VAC BETWEEN BLACK AND YELLOW


IF THEN
24VAC is present

This is correct – continue to Step 11

24VAC is not present

See Step 9B.

Check the harness plug connecting.

Check that cam on shaft rotates with
shaft.

Replace the damper board.

Ensure that cam is secure against end
switch.


Condition:
Damper rotates continuously

STEP 10B

ADJUST END SWITCH TO CAM CONTACT

















IF THEN
Damper stops in proper position

24 VAC should be open on a call for heat
and close during standby/

Damper does not stop in proper position

Replace damper assembly.