SBD TANK TYPE HEATERS
SERVICE HANDBOOK
Technical Training Department
Ashland City, TN ©2003
29
TROUBLESHOOTING THE EFFIKAL DAMPER (continued)
Condition:
Thermostat closed, damper open.
STEP 9B
A1 IS CORRECT, CHECK SERVICE SWITCH
POSITION
IF THEN
Switch is incorrect position
Replace damper board/motor assembly.
Switch is not in correct position
•
Adjust switch
•
Cycle thermostat to verify that damper
operation is correct.
Service
Switch
Damper
Open
Damper
Auto