beautypg.com

1 set_permanent_parameter – Siemens CP 243-2 User Manual

Page 81

background image

Command Interface

5-13

SIMATIC NET CP 243-2 AS-i Master
C79000-G8976-C142/02

5.2.1

Set_Permanent_Parameter

Purpose

With this call, a parameter value for the specified AS-i slave is transferred to the
CP 243-2 . The value is saved permanently as a configured value.

The configured parameter is not transferred immediately to the AS-i slave by the
CP 243-2. The configured parameter value is only transferred when the AS-i slave
is activated after turning on the power supply on the CP 243-2.

This call is not permitted for AS-i slaves that comply with the AS-i slave standard
profile 7.4. For these AS-i slaves, the AS-i master handles the AS-i slave
parameter assignment itself. In this case, the configured parameters are always
set to F H.

Structure of the Job Data in the Send Buffer

Bank

Byte

Meaning

Bit 7

Bit 4

Bit 3

Bit 0

2

0

Command number: 00

H

2

1

AS-i slave address

2

2

irrelevant

Parameter

Structure of the Job Data in the Receive Buffer

Bank

Byte

Meaning

2

0

Echo of the command number: 00

H

2

1

Command status