Siemens CP 243-2 User Manual
Page 73
![background image](/manuals/144217/73/background.png)
Command Interface
5-5
SIMATIC NET CP 243-2 AS-i Master
C79000-G8976-C142/02
Table 5-2
, continued
SI Q1.0, 1
//Select bank 5
BMW VW748, AQW0, 8
//V memory –> bank
RI Q1.0, 1
//Select bank 6
SI Q1.1, 1
//Select bank 6
BMW VW764, AQW0, 8
//V memory –> bank
SI Q1.0, 1
//Select bank 7
BMW VW780, AQW0, 8
//V memory –> bank
RI Q1.0, 3
//Select bank 8
SI Q1.3, 1
//Select bank 8
BMW VW796, AQW0, 8
//V memory –> bank
SI Q1.0, 1
//Select bank 9
BMW VW812, AQW0, 8
//V memory –> bank
RI Q1.0, 1
//Select bank 10
SI Q1.1, 1
//Select bank 10
BMW VW828, AQW0, 8
//V memory –> bank
SI Q1.0, 1
//Select bank 11
BMW VW844, AQW0, 8
//V memory –> bank
RI Q1.0, 2
//Select bank 12
SI Q1.2, 1
//Select bank 12
BMW VW860, AQW0, 8
//V memory –> bank
SI Q1.0, 1
//Select bank 13
BMW VW876, AQW0, 8
//V memory –> bank
RI Q1.0, 1
//Select bank 14
SI Q1.1, 1
//Select bank 14
BMW VW892, AQW0, 8
//V memory –> bank
SI Q1.0, 1
//Select bank 15
BMW VW908, AQW0, 8
//V memory –> bank
RI Q1.0,6
//Select bank 0
SI Q1.6, 1
//ASI_COM
//Fetch response from CP
LD Q1.6
//ASI_COM
A I1.6
//ASI_RESP
RI Q1.0, 6
//Select bank 2
SI Q1.1, 1
//Select bank 2
BMW AIW0, VW400, 8
//Bank –> V memory
SI Q1.0, 1
//Select bank 3
BMW AIW0, VW416, 8
//Bank –> V memory
RI Q1.0, 2
//Select bank 4
SI Q1.2, 1
//Select bank 4
BMW AIW0, VW432, 8
//Bank –> V memory
SI Q1.0, 1
//Select bank 5
BMW AIW0, VW448, 8
//Bank –> V memory
RI Q1.0, 1
//Select bank 6
SI Q1.1, 1
//Select bank 6
BMW AIW0, VW464, 8
//Bank –> V memory
SI Q1.0, 1
//Select bank 7
BMW AIW0, VW480, 8
//Bank –> V memory
RI Q1.0, 3
//Select bank 8
SI Q1.3, 1
//Select bank 8
BMW AIW0, VW496, 8
//Bank –> V memory