beautypg.com

20 read_extended_parameter_echo_list – Siemens CP 243-2 User Manual

Page 113

background image

Command Interface

5-45

SIMATIC NET CP 243-2 AS-i Master
C79000-G8976-C142/02

5.2.20

Read_Extended_Parameter_Echo_List

Purpose

When the parameters are transferred to the AS-i slaves, they return “echo values”
as the response. The read parameter echo list call reads out the echo values of all
AS-i slaves.

Structure of the Job Data in the Send Buffer

Bank

Byte

Meaning

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

2

0

Command number: 33

H

2

1

00

H

Structure of the Job Data in the Receive Buffer

Bank

Byte

Meaning

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

2

0

Echo of the command number 33

H

2

1

Command status

2

2

irrelevant

Par echo slave 1

2

3

Par echo slave 2

Par echo slave 3

2

4

Par echo slave 4

Par echo slave 5

2

5

Par echo slave 6

Parameters slave 7

2

6

Par echo slave 8

Par echo slave 9

2

7

Par echo slave 10

Par echo slave 11

2

8

Par echo slave 12

Par echo slave 13

2

9

Par echo slave 14

Par echo slave 15

2

10

Par echo slave 16

Par echo slave 17

2

11

Par echo slave 18

Par echo slave 19

2

12

Par echo slave 20

Par echo slave 21

2

13

Par echo slave 22

Par echo slave 23

2

14

Par echo slave 24

Par echo slave 25

2

15

Par echo slave 26

Par echo slave 27

2

0

Par echo slave 28

Par echo slave 29

3

1

Par echo slave 30

Par echo slave 31

3

2

irrelevant

Par echo slave 1B

3

3

Par echo slave 2B

Par echo slave 3B

3

4

Par echo slave 4B

Par echo slave 5B

3

5

Par echo slave 6B

Parameters slave 7B

3

6

Par echo slave 8B

Par echo slave 9B

3

7

Par echo slave 10B

Par echo slave 11B

3

8

Par echo slave 12B

Par echo slave 13B