2 slave display – Siemens CP 243-2 User Manual
Page 22
Technical Description and Installation Instructions
1-14
SIMATIC NET CP 243-2 AS-i Master
C79000-G8976-C142/02
1.8.2
Slave Display
Interpreting the Slave Display Status
You can switch over to the slave display mode used by pressing the DISPLAY
button. You switch from group to group by pressing the DISPLAY button again: The
slave display is active when at least one group LED is lit.
Characteristics of the Slave Display
S
If the CP 243-2 is in the configuration mode, all detected AS-i slaves are
displayed.
S
If the CP 243-2 is in the protected mode, all active AS-i slaves are displayed.
In the protected mode, failed or existing but unconfigured AS-i slaves are
indicated by the corresponding LED flashing.
Display Statuses in Detail
The AS-i slaves are displayed in groups of five. The three group LEDs indicate
which group of 5 is being displayed in binary code. The 5 LEDs of the slave display
then indicate the detected or active AS-i slaves within the group.
To find out which slaves are active, select the group of 5 (line) corresponding to the
lit group LEDs. The currently lit LEDs of the slave display then indicate which
slaves within this group are currently active.
If a group of B slaves is displayed, the “B” LED is also lit.