Interface to the User Program in the S7-200 CPU
2-19
SIMATIC NET CP 243-2 AS-i Master
C79000-G8976-C142/02
Bank 1: Diagnostics on the AS-Interface
The delta list of the AS-i slaves is indicated in this bank.
The delta list contains deviations of the existing AS-i slaves from the configuration
on the CP 243-2.
A set bit can indicate the following:
S
Missing slaves
S
Extra slaves (not in the configuration)
S
Slaves with incorrect I0/ID coding
The delta list is updated both in the configuration and in the protected mode.
The bytes and bits of the delta list are ordered as shown in the table below.
(m: start address of the analog input area of the CP 243-2)
Byte \ Bit
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Byte m+0 Slave 7
Slave 7A
Slave 6
Slave 6A
Slave 5
Slave 5A
Slave 4
Slave 4A
Slave 3
Slave 3A
Slave 2
Slave 2A
Slave 1
Slave 1A
Slave 0
Slave 0A
Byte m+1 Slave 15
Slave 15A
Slave 14
Slave 14A
Slave 13
Slave 13A
Slave 12
Slave 12A
Slave 11
Slave 11A
Slave 10
Slave 10A
Slave 9
Slave 9A
Slave 8
Slave 8A
Byte m+2 Slave 23
Slave 23A
Slave 22
Slave 22A
Slave 21
Slave 21A
Slave 20
Slave 20A
Slave 19
Slave 19A
Slave 18
Slave 18A
Slave 17
Slave 17A
Slave 16
Slave 16A
Byte m+3 Slave 31
Slave 31A
Slave 30
Slave 30A
Slave 29
Slave 29A
Slave 28
Slave 28A
Slave 27
Slave 27A
Slave 26
Slave 26A
Slave 25
Slave 25A
Slave 24
Slave 24A
Byte m+4 Slave 7B
Slave 6B
Slave 5B
Slave 4B
Slave 3B
Slave 2B
Slave 1B
Slave 0B
Byte m+5 Slave 15B Slave 14B Slave 13B Slave 12B Slave 11B
Slave 10B Slave 9B
Slave 8B
Byte m+6 Slave 23B Slave 22B Slave 21B Slave 20B Slave 19B Slave 18B Slave 17B Slave 16B
Byte m+7 Slave 31B Slave 30B Slave 29B Slave 28B Slave 27B Slave 26B Slave 25B Slave 24B
Banks 2–15: Response data on the AS-Interface
These banks contain the response data of the command calls. The data structures
used and the codings are described in Section 5.2. The number of banks used
depends on the particular command.
Banks 16–30: Reserved area
These areas are reserved for later expansions and cannot be used.
Bank 31: Binary input data of the AS-i slaves 1B – 31B
Via these analog input words, you have access to the binary inputs of the B slaves
(slaves with the extended addressing mode).
The structure of the input data is described in Section 3.1.