Appendix 2: initial value – MITSUBISHI ELECTRIC PAC-YG31CDA User Manual

Page 44

background image




The initial value of the property of each object is shown.

Object Object

Type

Instance

Number

Present Value

Note

On/Off (setup)

BO

xxxx01

OFF (0)

On/Off (state)

BI

xxxx02

OFF (0)

Alarm Signal

BI

xxxx03

Normal (0)

Error Code

MI

xxxx04

Normal (1)

Operation Mode (setup)

MO

xxxx05

Fan (3)

Operation Mode (state)

MI

xxxx06

Fan (3)

Fan Speed (setup)

MO

xxxx07

Low (1)

Fan Speed (state)

MI

xxxx08

Low (1)

Room Temp.

AI

xxxx09

69°F (21℃)

Set Temp.

AV

xxxx10

69°F (21℃)

Filter Signal

BI

xxxx11

Off (0)

Filter Signal Reset

BV

xxxx12

Reset (0)

Prohibition of local operation
(On/Off)

BV

xxxx13

Permit (0)

Prohibition of local operation
(Mode)

BV

xxxx14

Permit (0)

Prohibition of local operation
(Filter Reset)

BV

xxxx15

Permit (0)

Prohibition of local operation
(Set Temp)

BV

xxxx16

Permit (0)

Communication State

BI

xxxx20

Normal (0)

System Forced Off

BV

xx9921

Release (0)

Air Direction (setup)

MO

xxxx22

Horizontal (1)

Air Direction (state)

MI

xxxx23

Horizontal (1)

Notification Class

Notification Class

000003

-

Device

Device

000003 -

Appendix 2: Initial Value