8.8.2 Notification Setting

BMS carries out the monitor of the state, in order to know the state of Object of BACnetIF.
Notification is the function notified to the BACnet (or Building Automation System), when the value currently
supervised exceeds a limit or it changes to an alarm value. There are COV type and EVENT in Notification.

Item

Contents

Target object name

COV (Change Of Value)
Notification

Example) When the [RoomTemp] value
currently supervised changes, BACnet IF
send a COV notification message to the
BMS.

All
Except for
Notification Class and Device

EVENT Notification

When the decided specific conditions are
satisfied, it announces to a BMS.
Example1) When the [Alarm Signal] value
currently supervised changes to the alarm
value, BACnet IF send a notification
message to the BMS.
Example 2) When the [RoomTemp] value
currently supervised exceeds a limit,
BACnet IF sends a notification message to
the BMS.

All
Except for
Notification Class and Device


8.8.2.1 COV notification setup

The destination address of a COV notification message is setup.

The number of the address, which can be registered, is to 10.

Select the [COV Notification Settings] tab.

COV No.
Set the number

of COV

notification.

(1) Add COV notification address

Click the [Add] button. The [Notification Address] screen will open.