4.8 Setting functional list
The list of the setting functions of BACnet IF is arranged below.
Chapter 8 explains the usage of each function.
Setting information takes backup. For the backup procedure, refer to Appendix 3.
Item Details
G-50A Tab
G-50A and the air-conditioning unit for management are set up. (*1)
G-50A setup
The information on G-50A for management is set up.
G-50A number, IP address, Port number (80 fixation : for LAN communication of G-50A).
Group setup
The information on the group registered into G-50A is set up.
Group number, Apparatus attribute, Out Of Service
BACnet Tab
It sets up about BACnet communication.
Broadcast IP-Address
The IP address of a building management system is set up.
Timeserver IP-Address
The IP address of time synchronous origin is set up.
BACnet Application setup
The communication parameter of BACnet is set up. Port number (47808 fixation: for BACnet
communication), Venders ID (99 fixation), DeviceID APDU timeout, Number of times of APDU retries,
Check command (I-AM) transmitting interval
Notification function is set up.
COV Notification
COV number, IP address, Notification type
EVENT Notification
Processes ID, NClassID, Priority, IP address, Notification type
Event Notification setup
Conditions of Notification
COV Notification: COV number, Change increment setup
EVENT Notification : NClassID、Event-Enable、Limit-Enable、
Notification type, Time_Delay
System Tab
The function of a system is set up.
Unit of Temperature
The unit (Fahrenheit, Celsius) of the temperature data used by BACnet is switched.
Drive Mode Type
Use in operation mode "DRY" is set up.
Air Speed Type
Use of wind velocity "Mid2, Mid1" is set up.
Time
Set
The
notification to G-50A of a time synchronous notification is set up. (*2)
Auto Reboot
The execution time of automatic reboot is set up.
File menu
Execution of file operation and an end of a tool.
New Settings
An untitled setting file is newly created.
Open Settings
System information is loaded from the saved file.
Save Settings
System setting information is saved at a file (overwrite).
Save Settings As...
System setting information is saved at a file.
Exports
System setting information is outputted to a CSV file.
Properties
The IP address of the personal computer, which is setting up BACnetIF, is set up.
[127.0.0.1] is set up when BACnetIF is set up in the same personal computer as a setting tool.
Exit
A setting tool is ended.
BACnetIF menu
The contents of a system setting are transmitted between SetBACnet (setting tool) and BACnetIF.
Get Settings
System setting information is transmitted to BACnetIF.
Put Settings
System setting information is read from BACnetIF.
*1 Since the information on the set-up air-conditioning unit is not registered into G-50A, it is necessary to set it up on G-50A separately.
*2 Setup of "Timeserver IP-Address" is required for use of this function.