background image

4.8 Setting functional list

The list of the setting functions of BACnet IF is arranged below.

Chapter 8 explains the usage of each function.

Setting information takes backup. For the backup procedure, refer to Appendix 3.

Item Details

G-50A Tab

G-50A and the air-conditioning unit for management are set up. (*1)

G-50A setup

The information on G-50A for management is set up.

G-50A number, IP address, Port number (80 fixation : for LAN communication of G-50A).

Group setup

The information on the group registered into G-50A is set up.

Group number, Apparatus attribute, Out Of Service

BACnet Tab

It sets up about BACnet communication.

Broadcast IP-Address

The IP address of a building management system is set up.

Timeserver IP-Address

The IP address of time synchronous origin is set up.

BACnet Application setup

The communication parameter of BACnet is set up. Port number (47808 fixation: for BACnet

communication), Venders ID (99 fixation), DeviceID APDU timeout, Number of times of APDU retries,

Check command (I-AM) transmitting interval

Notification function is set up.

COV Notification

COV number, IP address, Notification type

EVENT Notification

Processes ID, NClassID, Priority, IP address, Notification type

Event Notification setup

Conditions of Notification

COV Notification: COV number, Change increment setup

EVENT Notification : NClassID、Event-Enable、Limit-Enable、

Notification type, Time_Delay

System Tab

The function of a system is set up.

Unit of Temperature

The unit (Fahrenheit, Celsius) of the temperature data used by BACnet is switched.

Drive Mode Type

Use in operation mode "DRY" is set up.

Air Speed Type

Use of wind velocity "Mid2, Mid1" is set up.

Time

Set

The

notification to G-50A of a time synchronous notification is set up. (*2)

Auto Reboot

The execution time of automatic reboot is set up.

File menu

Execution of file operation and an end of a tool.

New Settings

An untitled setting file is newly created.

Open Settings

System information is loaded from the saved file.

Save Settings

System setting information is saved at a file (overwrite).

Save Settings As...

System setting information is saved at a file.

Exports

System setting information is outputted to a CSV file.

Properties

The IP address of the personal computer, which is setting up BACnetIF, is set up.

[127.0.0.1] is set up when BACnetIF is set up in the same personal computer as a setting tool.

Exit

A setting tool is ended.

BACnetIF menu

The contents of a system setting are transmitted between SetBACnet (setting tool) and BACnetIF.

Get Settings

System setting information is transmitted to BACnetIF.

Put Settings

System setting information is read from BACnetIF.

*1 Since the information on the set-up air-conditioning unit is not registered into G-50A, it is necessary to set it up on G-50A separately.

*2 Setup of "Timeserver IP-Address" is required for use of this function.

14