9.4 Step 2: Initial setting of BACnet IF

LAN

Step 2

HUB

Power

supply unit

G-50A

BACnet IF

Ether BACnet

Building Automation System

(1) Set-up of BACnet IF

Make preparations to allow the PC to be operative in order to install BACnet IF. After performing the
set-up preparations, set up BACnet IF.

Note:

• For the set-up procedure, refer to Chapter 5.
• For safety, check the installation state/connection before turning the power ON.




(2) Check the G-50A IP address and PC (which uses BACnet IF)

Check the G-50A IP address. Check the IP address used for BACnet IFat the same time. Normally,
set the sub-net to "255.255.255.0".
A setup an IP address etc. should use and set up the function of OS of a network setup.

For a LAN dedicated to the G-50A system, it is recommended to set the IP address
within the following range. IP address decides that it does not overlap.

Models

IP address range

G-50A main unit

[192.168.1.1] to [192.168.1.40]

PC (using BACnet IF)

for BMS network: [192.168.2.1]
for G-50A system: [192.168.1.250]

* To connect to the existing LAN, set the IP address and sub-net mask set by the LAN manager.

(3) LAN connection confirmation

Check that the LAN cable is connected to the G-50A, PC (using BACnet IF), and hub, and that
power is supplied to the hub.

(4) Initial setting of BACnet IF

Start BACnet IF to execute the initial setting.

Note:

• For the initial setting method of BACnet IF, refer to Chapters 6 to 8.