(4) from G-50A

Click the [from G-50] button. The confirmation screen will open.
Click the [YES] button acquires group information from G-50A.

Note:
Separately, it is necessary to register groups into G-50A.



8.7.4 Group setup

8.7.4.1 Group Setup

Item Contents Set

value

Group No

Input the number of a group.

Default:

Null

Range: 1 to 50

Model

Select the model of a group.

IC:Indoor unit
LC: LOSSNAY unit

OA processing unit: select IC

Out Of Service *1

If the service mode of the group is changed
into OutOfService, the communication
message about the group will be
transmitted to neither G-50A nor a BMS.

Default: Off

Check mark is Off: Service mode
Check mark is On: OutOfService
mode

*1:Out Of Service in the case of maintenance or a test run.

Communication Message>

From BMS

: The instruction (System Forced OFF is excluded) from BMS is not transmitted to G-50A.

Monitoring for G-50A : Neither state change nor abnormality of the air-conditioning unit is notify.

Change Timing>

After ending BACnetIF, with [OutOfService] checked, a setup is reflected at the time of next BACnetIF starting.
If [OutOfServie] is checked and the [Online Operation] button is clicked, it will be immediately reflected in BACnetIF. →Refer to 8.7.4.2

Note:
Be sure to release OutOfService mode after maintenance or a test run.





8.7.4.2 Online Operation

Click the [Online Operation] button. The confirmation screen will open.

If it will be immediately reflected in BACnet IF, click the [True] button.

Click the [False] button, when that is not right.