Object Object

type

Instance
number *5)

Management item

Test procedure

Result

Prohibition of local
operation (Mode)

BV xxxx14 Inactive:

Permit

Active: Prohibit

- Change remote control hand operation (Mode) of
a group from BMS.
Then, it checks by G-50A whether the state of an
air-conditioning system is equal to the state where it
was operated by BMS.
- Change remote control hand operation (Mode) of
a specific group by G-50A.
Then, the state of BACnet IF is read from BMS
and it checks in the same state as G-50A.

Prohibition of local
operation (filter reset)

BV xxxx15 Inactive:

Permit

Active: Prohibit

- Change remote control hand operation (filter
reset) of a specific group by G-50A.
Then, the state of BACnet IF is read from BMS
and it checks in the same state as G-50A.

Prohibition of local
operation (Set Temp.)

BV xxxx16 Inactive:

Permit

Active: Prohibit

- Change remote control hand operation (Set
Temp) of a group from BMS.
Then, it checks by G-50A whether the state of an
air-conditioning system is equal to the state where it
was operated by BMS.
- Change remote control hand operation (Set
Temp) of a specific group by G-50A.
Then, the state of BACnet IF is read from BMS
and it checks in the same state as G-50A.

Communication State BI

xxxx20

Inactive: Normal
Active: Abnormal

- Remove the transmission line of LAN connected
to G-50A.
Then, a state is read from BMS and it checks in
Abnormalities (ACTIVE).
- Connect the transmission line of LAN to G-50A.
Then, the state of BACnet IF is read from BMS
and it checks in Normal (INACTIVE).
- Remove the transmission line of LAN connected
to G-50A.
Then, it checks whether Event Notification is
transmitted to BMS from PAC-YG31CDA.

System Forced Off

BV

xx9921

Inactive: Released
Active: Effective

- Change the system forced Off of a group from
BMS.
Then, it checks by G-50A whether the state of an
air-conditioning machine is equal to the state where
it was operated by BMS.

Air direction
(setup)

MO xxxx22 01:

Horizontal

02: Down 60%
03: Down 80%
04: Down100%
05: Swing

- Change the wind direction of a group from BMS.
Then, it checks by G-50A whether the state of an
air-conditioning machine is equal to the state where
it was operated by BMS.

Air direction
(state)

MI xxxx23 01:

Horizontal

02: Down 60%
03: Down 80%
04: Down100%
05: Swing

- Change the wind direction of a group by G-50A.
Then, the state of BACnet IF is read from BMS
and it checks in the same state as G-50A.

*1) It can use, if dry operation use is set up.

*2) It can use, if use of Mid1/Mid2 is set up.

*3) The group of LC serves as an item with an invalid attribute.

*4) As for the operation mode of the group of LC, an attribute serves as ventilation fixation.

*5) XXXX of an instance number consists of G50 number + group numbers.

*6) BMS:Building Management System