beautypg.com

FieldServer Envirotronics SystemsPlus FS-8700-88 User Manual

Page 9

background image

FS-8700-88 Envirotronics SystemsPlus

Page 9 of 49

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com

Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]

4.2.

Client Side Connection Descriptions

Section Title

Connections

Column Title

Function

Legal Values

Port

Specify which port the device is connected
to the FieldServer

P1-P8

1

Protocol

Specify protocol used

SystemsPlus

Baud*

Specify baud rate

300 – 19200, standard baud
rates only

Parity*

Specify parity

Even, Odd, None

Data_Bits*

Specify data bits

7, 8

Stop_Bits*

Specify stop bits

1, 2

Handshaking* Specify hardware handshaking

RTS, RTS/CTS, None

Poll _Delay*

Time between internal polls

0-32000 seconds, 1 second

Example

// Client Side Connections

Connections
Port,

Protocol,

Baud,

Parity,

Handshaking,

Poll_Delay

P1,

SystemsPlus,

19200,

None,

None,

0.100s

4.3.

Client Side Node Descriptors

Section Title

Nodes

Column Title

Function

Legal Values

Node_Name

Provide name for node

Up to 32 alphanumeric
characters

Protocol

Specify protocol used

SystemsPlus

Port

Specify which port the device is
connected to the FieldServer

P1-P8

1

Example

// Client Side Nodes

Nodes

Node_Name,

Protocol,

Port

SYSPLUS_01,

SystemsPlus,

P1



1

Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction

manual for details of the ports available on specific hardware.