4.2.
Client Side Connection Descriptions
Section Title
Connections
Column Title
Function
Legal Values
Port
Specify which port the device is connected
to the FieldServer
P1-P8
1
Protocol
Specify protocol used
SystemsPlus
Baud*
Specify baud rate
300 – 19200, standard baud
rates only
Parity*
Specify parity
Even, Odd, None
Data_Bits*
Specify data bits
7, 8
Stop_Bits*
Specify stop bits
1, 2
Handshaking* Specify hardware handshaking
RTS, RTS/CTS, None
Poll _Delay*
Time between internal polls
0-32000 seconds, 1 second
Example
// Client Side Connections
Connections
Port,
Protocol,
Baud,
Parity,
Handshaking,
Poll_Delay
P1,
SystemsPlus,
19200,
None,
None,
0.100s
4.3.
Client Side Node Descriptors
Section Title
Nodes
Column Title
Function
Legal Values
Node_Name
Provide name for node
Up to 32 alphanumeric
characters
Protocol
Specify protocol used
SystemsPlus
Port
Specify which port the device is
connected to the FieldServer
P1-P8
1
Example
// Client Side Nodes
Nodes
Node_Name,
Protocol,
Port
SYSPLUS_01,
SystemsPlus,
P1
1
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction
manual for details of the ports available on specific hardware.