Map descriptor example 89 - edit read aux, Map descriptor example 90 - edit read cycles – FieldServer Envirotronics SystemsPlus FS-8700-88 User Manual
Page 38
FS-8700-88 Envirotronics SystemsPlus
Page 38 of 49
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]
4.4.93.
Map Descriptor Example 89 - edit read aux.
// Client Side Mao Descriptors
Map Descriptor
Map_Descriptor_Name,
Data_Array_Name,
Data_Array_Offset,
Function, Node_Name,
SysPlus_Cmd,
Store_Data_Array_Name,
Store_Data_Array_Offset,
Length
Ed_Rd_Aux,
Rd_Triggers,
5,
art,
SYSPLUS_01,
Ed_Rd_Aux,
Ed_Rd_Aux,
0,
1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.
The retrieved data is stored as follows:
Offset from Store_Data_Array_Offset Description
0
Aux0 status
..
..
9
Aux9 status
4.4.94.
Map Descriptor Example 90 - edit read cycles
// Client Side Mao Descriptors
Map Descriptor
Map_Descriptor_Name,
Data_Array_Name,
Data_Array_Offset,
Function,
Node_Name,
SysPlus_Cmd,
Store_Data_Array_Name,
Store_Data_Array_Offset,
Length
Ed_Rd_Cycles,
Rd_Triggers,
6,
art,
SYSPLUS_01,
Ed_Rd_Cycles,
Ed_Rd_Cycles,
0,
1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.
The retrieved data is stored as follows:
Offset from Store_Data_Array_Offset Description
0
Number of cycles