Map descriptor example 29 - read auxs, Map descriptor example 31 - emergency stop – FieldServer Envirotronics SystemsPlus FS-8700-88 User Manual
Page 19
FS-8700-88 Envirotronics SystemsPlus
Page 19 of 49
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]
4.4.32.
Map Descriptor Example 29 - read auxs
// Client Side Map Descriptors
Map Descriptor
Map_Descriptor_Name,
Scan_Interval,
Data_Array_Name,
Data_Array_Offset,
Function,
Node_Name,
SysPlus_Data_Type,
Length
All_Aux_States,
0s,
All_Aux_States,
0,
rdbc,
SYSPLUS_01,
All_Auxs,
10
The retrieved aux states will be stored as follows in Data_Array_Name: (A value of 1 will be stored for “on” or 0 for “off”)
Offset from Data_Array_Offset Description
0
Aux_0 state
1
Aux_1 state
2
Aux_2 state
..
..
9
Aux_9 state
4.4.33.
Map Descriptor Example 30 - read alarm status alarm
// Client Side Map Descriptors
Map Descriptor
Map_Descriptor_Name,
Scan_Interval,
Data_Array_Name,
Data_Array_Offset,
Function,
Node_Name,
SysPlus_Data_Type,
SysPlus_Alarm_Name,
Length
Alarm_Sts_00,
0s,
Alarm_Statuses,
0,
rdbc,
SYSPLUS_01,
Alarm,
volt,
1
alarm is specified by the name under SysPlus_Alarm_Name. The status of the alarm will be stored as 1 for “OK” or 0 for “FAIL” in
Data_Array_Name at Data_Array_Offset.
4.4.34.
Map Descriptor Example 31 - emergency stop
// Client Side Map Descriptors
Map Descriptors
Map_Descriptor_Name,
Data_Array_Name,
Data_Array_Offset,
Function,
Node_Name,
SysPlus_Cmd,
Length
Emergency_Stop,
ProgSysControl,
0,
wrbx,
SYSPLUS_01,
Emergency_Stop,
1
Triggger this command by writing any value to Data_Array_Name at Data_Array_Offset.