4.4.29.
Map Descriptor Example 26 - set audible alarm = Boolean
// Client Side Map Descriptors
Map Descriptor
Map_Descriptor_Name,
Data_Array_Name,
Data_Array_Offset,
Function,
Node_Name,
SysPlus_Data_Type,
Length
Audible_Alarm,
Audible_Alarm_0,
0,
wrbx,
SYSPLUS_01,
Audible_Alarm,
1
A Boolean value of 1 for “on” or 0 for “off” must be written to Data_Array_Name at Data_Array_Offset to trigger this command.
4.4.30.
Map descriptor Example 27 - read software version
// Cleint Side Map Descriptors
Map Descriptor
Map_Descriptor_Name,
Scan_Interval,
Data_Array_Name,
Data_Array_Offset,
Function,
Node_Name,
SysPlus_Data_Type,
Length
Sw_Version,
0s,
Sw_Version,
0,
rdbc,
SYSPLUS_01,
Sw_Version,
1
4.4.31.
Map Descriptor Example 28 - read events
// Client Side Map Descriptors
Map Descriptor
Map_Descriptor_Name,
Scan_Interval,
Data_Array_Name,
Data_Array_Offset,
Function,
Node_Name,
SysPlus_Data_Type,
Length
All_Event_States,
0s,
All_Event_States,
0,
rdbc,
SYSPLUS_01,
All_Events,
10
The retrieved event states will be stored as follows in Data_Array_Name:
( A value of 1 will be stored for “on” or 0 for “off” )
Offset from Data_Array_Offset Description
0
Event_0 state
1
Event_1 state
2
Event_2 state
..
..
9
Event_9 state