4.4.23.

Map Descriptor Example 20 - set start time enabled = Boolean

// Client Side Map Descriptors

Map Descriptor

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

SysPlus_Data_Type,

Length

Start_Time_Ena,

Start_Time_Ena_0,

0,

wrbx,

SYSPLUS_01,

Start_Time_Ena,

1


A Boolean value of 1 for “Enabled” or 0 for “Disabled” must be written to Data_Array_Name at Data_Array_Offset to trigger this
command.

4.4.24.

Map Descriptor Example 21 - read stop time enabled

// Client Side Map Descriptors

Map Descriptor

Map_Descriptor_Name,

Scan_Interval,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

SysPlus_Data_Type,

Length

Stop_Time_Ena,

0s,

Stop_Time_Ena,

0,

rdbc,

SYSPLUS_01,

Stop_Time_Ena,

1


The stop time enabled status will be stored as 1 for “Enabled” or 0 for “Disabled” in Data_Array_Name at Data_Array_Offset.

4.4.25.

Map Descriptor Example 22 - set stop time enabled = Boolean

// Client Side Map Descriptors

Map Descriptor

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

SysPlus_Data_Type,

Length

Stop_Time_Ena,

Stop_Time_Ena_0,

0,

wrbx,

SYSPLUS_01,

Stop_Time_Ena,

1


A Boolean value of 1 for “Enabled” or 0 for “Disabled” must be written to Data_Array_Name at Data_Array_Offset to trigger this
command.