4.4.78.
Map Descriptor Example 75 - edit set duration = hour:minute:second
// Client Side Mao Descriptors
Map Descriptor
Map_Descriptor_Name,
Data_Array_Name,
Data_Array_Offset,
Function,
Node_Name,
SysPlus_Cmd,
Par_Data_Array_Name,
Par_Data_Array_Offset,
Length
Ed_Set_Duration,
Par_Bit_Triggers,
0,
awt,
SYSPLUS_01,
Ed_Set_Duration,
Ed_Set_Duration,
0,
1
This command is used by first writing the parameter data (hour:minute:second) and then triggering the command by writing any value
to Data_Array_Name at Data_Array_Offset.
Parameter data setup:
Offset from par_data_array_offset Description
0
Hour
1
Minute
2
Second
4.4.79.
Map Descriptor Example 76 - set start time = month/day hour:minute
// Client Side Mao Descriptors
Map Descriptor
Map_Descriptor_Name,
Data_Array_Name,
Data_Array_Offset,
Function, Node_Name,
SysPlus_Cmd,
Par_Data_Array_Name,
Par_Data_Array_Offset,
Length
Set_Start_Time,
Par_Bit_Triggers,
1,
awt,
SYSPLUS_01,
Set_Start_Time,
Set_Start_Time,
0,
1
This command is used by first writing the parameter data and then triggering the command by writing any value to Data_Array_Name
at Data_Array_Offset.
Parameter data setup:
Offset from par_data_array_offset Description
0
Month
1
Day
2
Hour
3
Minute