7 specifications, Environmental specification, Server specifications – HP DL785 User Manual
Page 81: Environmental specification server specifications
7 Specifications
In this section
•
“Environmental specification” (page 81)
•
“Server specifications” (page 81)
Environmental specification
Value
Specification
Temperature range
10°C to 35°C (50°F to 95°F)
1
Operating
-30°C to 60°C (-22°F to 140°F)
2
Non-operating
28°C (82.4°F)
Maximum wet bulb temperature
Relative humidity (noncondensing)
3
10% to 90% relative humidity (Rh), 28°C (82.4°F)
maximum wet bulb temperature, non-condensing.
Operating
5% to 95% relative humidity (Rh), 38.7°C (101.7°F)
maximum wet bulb temperature, non-condensing.
Non-operating
Altitude
3050 m (10,000 ft). This value may be limited by the type
and number of options installed. Maximum allowable
altitude change rate is 457 m/min (1500 ft/min).
Operating
9144 m (30,000 ft). Maximum allowable altitude change
rate is 457 m/min (1500 ft/min).
Non-operating
1
10° to 35°C (50° to 95°F) at sea level with an altitude derating of 1.0°C per every 305 m (1.8°F per every 1000 ft) above
sea level to a maximum of 3050 m (10,000 ft), no direct sustained sunlight. Maximum rate of change is 10°C/hr
(18°F/hr). The upper limit may be limited by the type and number of options installed.
System performance may be reduced if operating with a fan fault or above 30°C (86°F).
2
Maximum rate of change is 20°C/hr (36°F/hr).
3
Storage maximum humidity of 95% is based on a maximum temperature of 45°C (113°F). Altitude maximum for
storage corresponds to a pressure minimum of 70 KPa.
Server specifications
Value
Specification
Dimension
30.58 cm (12.04 in)
Height
69.6 cm (27.4 in)
Depth
44 cm (17.32 in)
Width
72 kg (160 lbs)
Weight (maximum
1
)
67 kg (147 lbs)
Weight (minium
2
)
High line
3
200 - 240 V ac
Low line
100 - 120 V ac
Input requirement
180 - 264 V ac
90 - 132 V ac
Rated input voltage
Environmental specification
81