CAPACITY RATINGS

UNIT 580D

NOMINAL

TONS

STANDARD

CFM

NET COOLING

CAPACITY (Btuh)

TOTAL

kW

SEER*

EER

SOUND

RATING

(Bels)

Belt Drive

Direct Drive

036

3

1200

35,000

4.0

10.0

9.7

8.7

8.2

048

4

1600

47,000

5.5

10.0

9.7

8.6

8.2

060

5

2000

57,000

6.7

10.0

9.7

8.5

8.2

UNIT 580D

NOMINAL

TONS

STANDARD

CFM

NET COOLING

CAPACITY (Btuh)

TOTAL

kW

EER

SOUND

IPLV

RATING

(Bels)

072

6

2100

70,000

7.9

8.9

8.4

090

7

1

2

2800

85,000

9.6

8.9

8.6

9.35

102

8

1

2

3000

99,000

11.0

9.0

8.6

9.00

120

10

4000

117,000

13.0

9.0

8.8

9.35

150

12

1

2

4500

145,000

15.8

9.2

8.8

9.65

UNIT 579F

NOMINAL

TONS

NET COOLING

TOTAL

kW

EER

SOUND

IPLV

CAPACITY

RATING

(Btuh)

(Bels)

180

15

178,000

20.7

8.6

8.8

10.70

216

18

190,000

20.9

9.1

8.8

9.50

240

20

220,000

25.9

8.5

9.4

8.30

300

25

268,000

31.2

8.5

9.5

8.40

LEGEND

ARI

Air Conditioning and Refrigeration Institute

Bels

Sound Levels (1 bel = 10 decibels)

EER

Energy Efficiency Ratio

IPLV

Integrated Part-Load Values

SEER — Seasonal Energy Efficiency Ratio

*Applies only to units with capacity of 65,000 Btuh or less.

†The IPLV only applies to two-stage cooling units.

NOTES:
Rated in accordance with ARI Standards 210/240-89 or 360-86 (for 150-240 units) and 270-84.
Ratings are net values, reflecting the effects of circulating fan heat.
Ratings are based on:

Cooling Standard: 80 F db, 67 F wb indoor entering-air temperature and 95 F db air entering outdoor unit.
IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and 80 F db outdoor entering-air temperature.

6