beautypg.com

Operating sequence – Bryant 579F User Manual

Page 52

background image

ELECTRICAL DATA — 579F180-300

UNIT
579F

NOMINAL
VOLTAGE

(60 Hz)

VOLTAGE

RANGE

COMPRESSOR

OFM

IFM

POWER

EXHAUST

COMBUSTION
FAN MOTOR**

POWER SUPPLY

NO. 1

NO. 2

Min

Max

RLA

LRA

RLA

LRA

Qty

Hp

FLA

(ea)

FLA

FLA

LRA

FLA

MCA

MOCP†

180

(15 Tons)

208/230

(3 phase)

187

254

61.0

266

3

1

2

1.70

10.5/10.5

0.57

92/92

150/150

4.6

18.8

0.57

96/96

150/150

460

(3 phase)

414

508

28.0

120

3

1

2

0.08

4.8

0.30

42

70

2.3

6.0

0.30

45

70

575

(3 phase)

518

632

23.0

96

3

1

2

0.75

3.9

0.57

35

50

2.1

4.8

0.57

37

60

216

(18 Tons)

208/230

(3 phase)

187

254

28.3

205

25.0

185

3

1

2

1.70

15.8/15.8

0.57

81/81

100/100

4.6

18.8

0.57

86/86

110/110

460

(3 phase)

414

508

14.4

104

12.4

89

3

1

2

0.80

7.9

0.30

41

50

2.3

6.0

0.30

43

50

575

(3 phase)

518

632

11.4

78

10.4

78

3

1

2

0.75

6.0

0.57

33

40

2.1

4.8

0.57

35

45

240

(20 Tons)

208/230

(3 phase)

187

254

34.5

239

28.3

205

2

1

5.50

25.0/25.0

0.57

107/107

125/125

4.6

18.8

0.57

112/112

125/125

460

(3 phase)

414

508

17.0

119

14.4

104

2

1

2.80

13.0

0.30

54

70

2.3

6.0

0.30

57

70

575

(3 phase)

518

632

15.2

111

11.4

78

2

1

3.40

10.0

0.57

47

60

2.1

4.8

0.57

49

60

300

(25 Tons)

208/230

(3 phase)

187

254

43.6

228

43.6

228

2

1

5.50

28.0/28.0

0.57

137/137

175/175

4.6

18.8

0.57

142/142

175/175

460

(3 phase)

414

508

22.1

114

22.1

114

2

1

2.80

14.6

0.30

70

90

2.3

6.0

0.30

72

90

575

(3 phase)

518

632

17.9

91

17.9

91

2

1

3.40

13.0

0.57

60

70

2.1

4.8

0.57

62

80

LEGEND

CSA

Canadian Standards Association

CUL

Underwriters’ Laboratory Canada

FLA

Full Load Amps

HACR

Heating, Air Conditioning and Refrigeration

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

*Used to determine minimum disconnect size per NEC.

†Fuse or HACR circuit breaker.

**The 579F240 and 300 high-heat units have 2 combustion-fan motors.

036-150 Only

180-300 Only

180-300 Only

036-072 Only

090-150 Only

NOTES:
1. In compliance with NEC requirements for multimotor and combination load

equipment (refer to NEC Articles 430 and 440), the overcurrent protective de-
vice for the unit shall be fuse or HACR breaker. Canadian units may be fuse or
circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater
than 2%.

Use the following formula to determine the percent voltage imbal-

ance.

% Voltage Imbalance

max voltage deviation from average voltage

= 100 x

average voltage

EXAMPLE: Supply voltage is 460-3-60.

AB =452 v
BC =464 v
AC =455 v

452 +464 +455

Average Voltage =

3

1371

=

3

= 457

NOTE: The 575-v 580D036-150 units are CSA or CUL only.

Determine maximum deviation from average voltage.

(AB) 457 - 452 = 5 v
(BC) 464 - 457 = 7 v
(AC) 457 - 455 = 2 v

Maximum deviation is 7 v.

Determine percent voltage imbalance.

7

% Voltage Imbalance = 100 x

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum al-
lowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact
your local electric utility company immediately.

OPERATING SEQUENCE

COOLING, UNITS WITHOUT ECONOMIZER — When thermostat
calls for cooling, terminals G and Y1 are energized. The indoor
(evaporator) fan contactor (IFC) and compressor contactor no. 1
(C1) are energized, and evaporator-fan motor, compressor no. 1
(580D036-150

and

579F216-300)

or

unloaded

compressor

(579F180), and condenser fan(s) start. The condenser-fan motor(s)
runs continuously while unit is cooling. For units with 2 stages of
cooling, if the thermostat calls for a second stage of cooling by en-
ergizing Y2, compressor contactor no. 2 (C2) is energized and com-
pressor

no.

2

starts

(580D090-150

and

579F216-300)

or

compressor no. 1 runs fully loaded (579F180).

HEATING, UNITS WITHOUT ECONOMIZER (580D036-150) —
When the thermostat calls for heating, terminal W1 is energized. In
order to prevent thermostat short-cycling, the unit is locked into the

Heating mode for at least 1 minute when W1 is energized. The
induced-draft motor (IDM) is then energized and the burner ignition
sequence begins. The indoor (evaporator) fan motor (IFM) is ener-
gized 45 seconds after a flame is ignited. On units equipped for two
stages of heat, when additional heat is needed, W2 is energized
and the high-fire solenoid on the main gas valve (MGV) is ener-
gized. When the thermostat is satisfied and W1 is deenergized, the
IFM stops after a 45-second time-off delay.

HEATING, UNITS WITHOUT ECONOMIZER (579F180-300)
NOTE:
The 579F180-300 units have 2 stages of heat.

Set thermostat system switch at HEAT or AUTO. position and set
fan switch to AUTO. position for heating.

52