AIR DELIVERY — HORIZONTAL DISCHARGE UNITS (cont)
580D150 (12
1
⁄
2
TON)
Airflow
(Cfm)
Standard and Alternate Belt Drive Motors
External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
1.2
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
3700
677
1.20
1129
748
1.43
1316
810
1.65
1498
869
1.89
1700
928
2.17
1940
984
2.43
2166
3800
691
1.28
1194
761
1.52
1390
822
1.75
1582
880
1.98
1776
937
2.28
2035
993
2.55
2272
3900
705
1.37
1267
773
1.62
1473
834
1.86
1674
891
2.08
1862
947
2.39
2131
1002
2.66
2370
4000
720
1.47
1349
786
1.71
1548
847
1.97
1768
902
2.19
1957
957
2.50
2228
1011
2.79
2485
4100
734
1.56
1423
800
1.82
1641
860
2.09
1871
914
2.31
2061
967
2.60
2316
1021
2.91
2593
4200
749
1.66
1506
813
1.92
1725
873
2.21
1974
926
2.44
2175
978
2.71
2414
1030
3.04
2710
4300
764
1.77
1598
826
2.04
1828
886
2.33
2079
938
2.57
2290
989
2.83
2521
1040
3.18
2837
4400
779
1.88
1691
840
2.16
1931
899
2.46
2193
951
2.71
2414
1000
2.96
2638
1050
3.31
2955
4500
793
1.99
1785
854
2.28
2035
912
2.59
2307
963
2.86
2548
1012
3.09
2755
1061
3.43
3065
4600
808
2.11
1888
868
2.42
2158
925
2.73
2459
975
3.00
2674
1024
3.25
2901
1071
3.56
3184
4700
822
2.24
2000
882
2.56
2281
937
2.86
2548
988
3.16
2819
1036
3.42
3056
1082
3.70
3313
4800
837
2.37
2114
896
2.71
2414
950
3.00
2674
1001
3.32
2964
1048
3.59
3212
1093
3.86
3461
4900
852
2.51
2237
910
2.86
2548
963
3.15
2810
1014
3.48
3111
1060
3.76
3368
1105
4.02
3609
5000
867
2.65
2361
924
3.01
2683
977
3.30
2946
1027
3.65
3267
1073
3.94
3535
1117
4.20
3776
5100
882
2.79
2485
938
3.17
2828
990
3.46
3092
1040
3.82
3424
1085
4.12
3702
1129
4.40
3962
5200
896
2.95
2629
952
3.33
2973
1003
3.63
3248
1053
4.00
3590
1098
4.30
3869
1141
4.60
4148
5300
911
3.11
2773
967
3.50
3129
1017
3.80
3405
1066
4.18
3757
1111
4.50
4055
1153
4.80
4335
5400
926
3.27
2919
981
3.68
3294
1030
3.98
3572
1079
4.35
3916
1124
4.70
4270
1166
5.01
4531
5500
940
3.44
3074
995
3.86
3461
1044
4.17
3748
1092
4.54
4093
1137
4.91
4437
1178
5.22
4726
5600
955
3.62
3239
1010
4.04
3627
1058
4.38
3943
1105
4.73
4270
1150
5.12
4633
1190
5.44
4930
5700
970
3.80
3405
1024
4.23
3804
1072
4.59
4139
1118
4.93
4456
1163
5.34
4837
1203
5.67
5143
5800
985
3.99
3581
1039
4.42
3981
1086
4.80
4335
1131
5.14
4652
1176
5.56
5041
—
—
—
5900
1000
4.18
3757
1053
4.62
4167
1100
5.02
4540
1144
5.36
4856
—
—
—
—
—
—
6000
1015
4.39
3953
1068
4.83
4363
1114
5.25
4754
1158
5.58
5060
—
—
—
—
—
—
6100
1030
4.59
4139
1083
5.04
4558
1128
5.48
4967
—
—
—
—
—
—
—
—
—
6200
1046
4.81
4344
1097
5.26
4763
1142
5.71
5180
—
—
—
—
—
—
—
—
—
580D150 (12
1
⁄
2
TON) (cont)
Airflow
(Cfm)
Standard and Alternate Belt Drive Motors
External Static Pressure (in. wg)
1.4
1.6
1.8
2.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
3700
1036
2.68
2387
1080
2.90
2548
1114
3.07
2737
1135
3.17
2828
3800
1046
2.81
2503
1092
3.05
2719
1129
3.25
2901
1156
3.39
3028
3900
1055
2.94
2620
1102
3.20
2855
1143
3.42
3056
1174
3.59
3212
4000
1064
3.07
2737
1112
3.34
2983
1155
3.59
3212
1190
3.80
3405
4100
1072
3.20
2855
1121
3.49
3120
1165
3.76
3368
1203
3.99
3581
4200
1081
3.34
2983
1130
3.64
3258
1175
3.92
3516
1215
4.18
3757
4300
1090
3.48
3111
1139
3.79
3396
1185
4.08
3664
1226
4.36
3925
4400
1100
3.63
3248
1148
3.94
3535
1194
4.25
3822
1236
4.54
4093
4500
1109
3.78
3387
1157
4.09
3674
1203
4.42
3981
1246
4.72
4260
4600
1119
3.93
3525
1166
4.26
3832
1212
4.58
4130
1255
4.91
4437
4700
1129
4.09
3674
1175
4.43
3990
1221
4.76
4298
1264
5.09
4605
4800
1139
4.24
3813
1185
4.60
4148
1230
4.93
4456
1273
5.28
4782
4900
1150
4.38
3943
1194
4.77
4307
1239
5.12
4633
1282
5.47
4958
5000
1161
4.54
4093
1204
4.95
4475
1248
5.31
4810
1291
5.66
5133
5100
1172
4.71
4251
1214
5.13
4642
1257
5.51
4995
—
—
—
5200
1183
4.91
4419
1225
5.29
4791
1267
5.70
5170
—
—
—
5300
1194
5.08
4596
1236
5.47
4958
—
—
—
—
—
—
5400
1206
5.29
4791
1247
5.65
5124
—
—
—
—
—
—
5500
1218
5.52
4958
—
—
—
—
—
—
—
—
—
5600
1230
5.75
5124
—
—
—
—
—
—
—
—
—
5700
—
—
—
—
—
—
—
—
—
—
—
—
5800
—
—
—
—
—
—
—
—
—
—
—
—
5900
—
—
—
—
—
—
—
—
—
—
—
—
6000
—
—
—
—
—
—
—
—
—
—
—
—
6100
—
—
—
—
—
—
—
—
—
—
—
—
6200
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
Bhp
— Brake Horsepower Input to Fan
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 6.)
2.
indicates alternate motor and/or drive required.
3.
indicates field-supplied motor and drive required.
4.
indicates maximum usable bhp/watts of standard motor and drive.
5.
indicates maximum usable bhp/watts of alternate motor and/or drive.
6. Standard drive range is 860 to 1080 rpm. Alternate drive range is 900 to
1260 rpm. All other rpms require a field-supplied drive.
7. Values include losses for filters, unit casing, and wet coils.
8. Maximum continuous bhp is 4.2 for the standard motor and 5.25 for the al-
ternate motor. The maximum continuous watts are 3775 for the standard mo-
tor and 4400 for the alternate motor. Extensive motor and electrical testing on
these units ensures that the full range of the motor can be utilized with con-
fidence. Using your fan motors up to the wattage ratings shown will not result
in nuisance tripping or premature motor failure. Unit warranty will not be af-
fected. See Evaporator-Fan Motor Performance table on page 60 for addi-
tional information.
9. Use of a field-supplied motor may affect wire sizing. Contact your local rep-
resentative to verify.
10. Interpolation is permissible. Do not extrapolate.
11. Minimum allowable cfm is 300 cfm/ton.
45