Air delivery — vertical discharge units (cont) – Bryant 579F User Manual
Page 33

AIR DELIVERY — VERTICAL DISCHARGE UNITS (cont)
580D072 (6 TON)
Airflow
(Cfm)
Standard Belt Drive Motor
External Static Pressure (in. wg)
0.1
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1800
942
0.70
646
978
0.66
700
1063
0.82
771
1147
0.97
891
1248
1.20
1081
1322
1.33
1190
1900
982
0.80
739
1023
0.78
779
1097
0.91
843
1175
1.11
1006
1266
1.29
1156
1356
1.47
1310
2000
1022
0.91
835
1068
0.90
867
1132
1.01
924
1218
1.23
1106
1303
1.41
1258
1397
1.52
1353
2100
1063
0.99
916
1115
1.00
998
1180
1.17
1056
1261
1.35
1207
1340
1.53
1361
1428
1.66
1473
2200
1104
1.13
1039
1159
1.15
1081
1214
1.28
1148
1310
1.52
1353
1375
1.63
1447
1459
1.80
1595
2300
1130
1.26
1156
1202
1.29
1140
1248
1.38
1233
1358
1.69
1499
1410
1.72
1526
1488
1.93
1709
2400
1174
1.37
1258
1237
1.41
1224
1292
1.55
1378
1392
1.81
1604
1460
1.90
1683
1532
2.14
1892
2500
1201
1.48
1361
1272
1.53
1335
1335
1.71
1517
1427
1.94
1718
1518
2.16
1910
1575
2.35
2076
2600
1246
1.62
1491
1320
1.68
1482
1368
1.81
1604
1458
2.06
1823
1562
2.42
2136
1620
2.59
2283
2700
1285
1.75
1613
1361
1.82
1595
1400
1.91
1691
1490
2.19
1936
1602
2.64
2326
1666
2.85
2504
2800
1304
1.87
1726
1402
1.95
1639
1439
2.08
1840
1543
2.43
2145
1642
2.86
2512
—
—
—
2900
1345
2.07
1910
1446
2.16
1814
1477
2.16
1989
1585
2.65
2335
—
—
—
—
—
—
3000
1378
2.26
2084
1489
2.36
2032
1529
2.52
2223
1598
2.73
2444
—
—
—
—
—
—
580D072 (6 TON) (cont)
Airflow
(Cfm)
Standard Belt Drive Motor
External Static Pressure (in. wg)
1.2
1.4
1.6
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1800
1395
1.46
1301
1475
1.56
1387
1542
1.71
1517
1900
1430
1.58
1404
1504
1.69
1499
1556
1.82
1613
2000
1459
1.67
1482
1532
1.82
1613
1588
1.97
1744
2100
1489
1.80
1595
1567
1.99
1761
1626
2.16
1910
2200
1528
1.95
1726
1603
2.17
1919
1666
2.37
2093
2300
1561
2.13
1884
1637
2.35
2076
1710
2.54
2272
2400
1584
2.28
2015
1671
2.55
2249
1756
2.70
2467
2500
1633
2.53
2232
1698
2.72
2405
—
—
—
2600
1675
2.77
2436
—
—
—
—
—
—
2700
—
—
—
—
—
—
—
—
—
2800
—
—
—
—
—
—
—
—
—
2900
—
—
—
—
—
—
—
—
—
3000
—
—
—
—
—
—
—
—
—
LEGEND
Bhp
— Brake Horsepower Input to Fan
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required. (See Note 4.)
2.
indicates field-supplied motor and drive required.
3.
indicates maximum usable bhp/watts.
4. Standard motor drive range is 1070 to 1460 rpm. All other rpms require a field-
supplied drive.
5. Values include losses for filters, unit casing, and wet coils.
6. Maximum continuous bhp is 2.40 and the maximum continuous watts are 2120.
Extensive motor and electrical testing on these units ensures that the full range
of the motor can be utilized with confidence. Using your fan motors up to the
wattage ratings shown will not result in nuisance tripping or premature motor
failure. Unit warranty will not be affected. See Evaporator-Fan Motor Perfor-
mance table on page 60 for additional information.
7. Use of a field-supplied motor may affect wire sizing. Contact your local repre-
sentative to verify.
8. Interpolation is permissible. Do not extrapolate.
9. Minimum allowable cfm is 300 cfm/ton.
33