AIR DELIVERY — 579F180-300 UNITS
579F180 (15 TON)
Airflow
(Cfm)
Standard Belt-Drive Motor; 208/230-V and 460 V Units
External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
1.2
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
4500
801
1.05
933
890
1.26
1119
971
1.46
1297
1050
1.67
1483
1125
1.88
1670
1200
2.12
1883
4800
843
1.25
1110
928
1.47
1306
1006
1.68
1492
1081
1.90
1687
1153
2.13
1892
1223
2.36
2096
5100
885
1.47
1306
968
1.70
1510
1043
1.93
1714
1114
2.16
1918
1183
2.40
2131
1250
2.64
2345
5400
927
1.71
1519
1008
1.95
1732
1080
2.20
1954
1148
2.44
2167
1214
2.69
2389
1279
2.94
2611
5700
971
1.98
1758
1049
2.24
1989
1118
2.50
2220
1134
2.75
2442
1247
3.01
2673
1309
3.28
2913
6000
1016
2.28
2025
1091
2.55
2265
1158
2.83
2513
1222
3.10
2753
1282
3.36
2984
1342
3.64
3233
6300
1059
2.60
2309
1133
2.89
2567
1198
3.17
2815
1259
3.46
3073
1318
3.74
3321
1375
4.02
3570
6600
1104
2.96
2629
1174
3.26
2895
1239
3.56
3162
1297
3.86
3428
1355
4.15
3686
—
—
—
6900
1150
3.35
2975
1218
3.67
3259
1281
3.98
3535
—
—
—
—
—
—
—
—
—
7200
1194
3.77
3348
1260
4.10
3641
—
—
—
—
—
—
—
—
—
—
—
—
7500
1238
4.23
3758
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
579F180 (15 TON) (cont)
Airflow
(Cfm)
Standard Belt-Drive Motor; 208/230-V and 460-V Units
External Static Pressure (in. wg)
1.4
1.6
1.8
2.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
4500
1275
2.39
2123
1349
2.70
2398
1421
3.03
2691
1490
3.39
3011
4800
1293
2.62
2327
1364
2.92
2593
1433
3.24
2877
1501
3.59
3188
5100
1316
2.90
2575
1382
3.18
2824
1448
3.49
3099
1514
3.86
3428
5400
1342
3.20
2842
1403
3.47
3082
1466
3.77
3348
1529
4.16
3694
5700
1370
3.54
3144
1429
3.81
3384
1487
4.11
3650
—
—
—
6000
1401
3.92
3481
1458
4.20
3730
—
—
—
—
—
—
6300
—
—
—
—
—
—
—
—
—
—
—
—
6600
—
—
—
—
—
—
—
—
—
—
—
—
6900
—
—
—
—
—
—
—
—
—
—
—
—
7200
—
—
—
—
—
—
—
—
—
—
—
—
7500
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
Bhp
— Brake Horsepower Input to Fan
Watts — Input Watts to Motor
NOTES:
1. Factory shipped motor drive range is 1194 to 1526 rpm. Other rpms require a
field-supplied drive.
2. Static pressure losses (i.e., economizer) must be added to external static pres-
sure before entering Air Delivery table.
3. Interpolation is permissible. Do not extrapolate.
4. Maximum continuous bhp is 4.25 and the maximum continuous watts are 3775.
Extensive motor and drive testing on these units ensures that the full horse-
power range of the motor can be utilized with confidence. Using your fan mo-
tors up to the watts rating shown will not result in nuisance tripping or
premature motor failure. Unit warranty will not be affected.
579F180 (15 TON)
Airflow
(Cfm)
Standard Belt-Drive Motor, 575-V Units
External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
1.2
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
4500
801
1.05
933
890
1.26
1119
971
1.46
1297
1050
1.67
1483
1125
1.88
1670
1200
2.12
1883
4800
843
1.25
1110
928
1.47
1306
1006
1.68
1492
1081
1.90
1687
1153
2.13
1892
1223
2.36
2096
5100
885
1.47
1306
968
1.70
1510
1043
1.93
1714
1114
2.16
1918
1183
2.40
2131
1250
2.64
2345
5400
927
1.71
1519
1008
1.95
1732
1080
2.20
1954
1148
2.44
2167
1214
2.69
2389
1279
2.94
2611
5700
971
1.98
1758
1049
2.24
1989
1118
2.50
2220
1134
2.75
2442
1247
3.01
2673
1309
3.28
2913
6000
1016
2.28
2025
1091
2.55
2265
1158
2.83
2513
1222
3.10
2753
1282
3.36
2984
—
—
—
6300
1059
2.60
2309
1133
2.89
2567
1198
3.17
2815
—
—
—
—
—
—
—
—
—
6600
1104
2.96
2629
1174
3.26
2895
—
—
—
—
—
—
—
—
—
—
—
—
6900
1150
3.35
2975
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
7200
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
7500
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
579F180 (15 TON) (cont)
Airflow
(Cfm)
Standard Belt-Drive Motor, 575-V Units
External Static Pressure (in. wg)
1.4
1.6
1.8
2.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
4500
1275
2.39
2123
1349
2.70
2398
1421
3.03
2691
1490
3.39
3011
4800
1293
2.62
2327
1364
2.92
2593
1433
3.24
2877
—
—
—
5100
1316
2.90
2575
1382
3.18
2824
—
—
—
—
—
—
5400
1342
3.20
2842
—
—
—
—
—
—
—
—
—
5700
—
—
—
—
—
—
—
—
—
—
—
—
6000
—
—
—
—
—
—
—
—
—
—
—
—
6300
—
—
—
—
—
—
—
—
—
—
—
—
6600
—
—
—
—
—
—
—
—
—
—
—
—
6900
—
—
—
—
—
—
—
—
—
—
—
—
7200
—
—
—
—
—
—
—
—
—
—
—
—
7500
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
Bhp
— Brake Horsepower Input to Fan
Watts — Input Watts to Motor
NOTES:
1. Factory shipped motor drive range is 1201 to 1462 rpm. Other rpms require a
field-supplied drive.
2. Static pressure losses (i.e., economizer) must be added to external static pres-
sure before entering Air Delivery table.
3. Interpolation is permissible. Do not extrapolate.
4. Maximum continuous bhp is 3.45 and the maximum continuous watts are 3065.
Extensive motor and drive testing on these units ensures that the full horse-
power range of the motor can be utilized with confidence. Using your fan mo-
tors up to the watts rating shown will not result in nuisance tripping or
premature motor failure. Unit warranty will not be affected.