I. Install Vertical Termination Cap

• Attach the vertical termination cap by sliding the inner

collar of the cap into the inner flue of the pipe section

while placing the outer collar of the cap over the outer

flue of the pipe section.

• Secure the cap by driving three self-tapping screws

(supplied) through the pilot holes in the outer collar of

the cap into the outer flue of the pipe (see Figure 10.18).

J. Install Decorative Wall Components (SLP

only)

A decorative wall thimble can be installed on wall through

which the vent passes. The decorative wall thimble is used

to cover the wall shield firestop.
• Slide the decorative wall thimble over the last section of

horizontal pipe before connecting the termination cap to

the pipe.

Once the pipe section and the termination cap have

been connected, slide the wall thimble up to the interior

wall surface and attach with screws provided. See Figure

10.19.

Important Notice: Heat shields may not be field constructed.

K. Heat Shield Requirements for Horizontal

Termination

WARNING! Risk of Fire! To prevent overheating and fire,

heat shields must extend through the entire wall thick-

ness.

DO NOT remove the heat shields attached to the

wall shield firestop and the horizontal termination cap

(shown in Figure 10.20).

• Heat shields must overlap 1-1/2 in. (38 mm) mini-

mum.

There are two sections of the heat shield. One section

is factory-attached to the wall shield firestop. The other

section is factory-attached to the cap. See Figure 10.20.
If the wall thickness does not allow the required 1-1/2 in.

(38 mm) heat shield overlap when installed, an extended

heat shield must be used.
• If the wall thickness is less than 4 in./102 mm (DVP)

or 4-3/8 in./ 111 mm (SLP), the heat shields on the cap

and wall shield firestop must be trimmed. A minimum

1-1/2 in. (38 mm) overlap MUST be maintained.

• Use an extended heat shield if the finished wall thickness

is greater than 7-1/4 in. (184 mm).

• The extended heat shield may need to be cut to length

maintaining sufficient length for a 1-1/2 in. (38 mm)

overlap between heat shields.

• Attach the extended heat shield to either of the existing

heat shields using the screws supplied with the extended

heat shield. Refer to vent components diagrams in the

back of this manual.

• Rest the small leg on the extended heat shield on top

of the pipe section to properly space it from the pipe

section.