Number of analog input cards
Time to complete one full
scan
(in milliseconds)
8
1700
9
1900
10
2100
11
2300
12
2500
13
2700
14
2900
15
3100
16
3300
Status Indicators
Status LEDs
Four LEDs on the CPU module (shown in Figure 30) indicate the operating status of the controller and are
described in Table 18.
Table 18 Controller status LEDs
Designation
State
Indication
POWER
Steady on
Power is applied to the controller backplane.
Blinking
Diagnostic indication. See NOTE.
LoBAT
On
The CPU battery is low and needs replacement.
FORCE
On
One or more function block output values have been forced.
RUN
On
Controller is in RUN mode.
Blinking
Controller is in OFFLINE mode
Off
Controller is in PROGRAM mode.
OR
If POWER LED is blinking a fault has been detected in
controller. See NOTE.