beautypg.com

Status indicators – Honeywell UMC800 User Manual

Page 67

background image

Operation

Status Indicators

Release F

UMC800 Controller Installation and User Guide

59

4/01

Number of analog input cards

Time to complete one full

scan

(in milliseconds)

8

1700

9

1900

10

2100

11

2300

12

2500

13

2700

14

2900

15

3100

16

3300

Status Indicators

Status LEDs

Four LEDs on the CPU module (shown in Figure 30) indicate the operating status of the controller and are
described in Table 18.

Table 18 Controller status LEDs

Designation

State

Indication

POWER

Steady on

Power is applied to the controller backplane.

Blinking

Diagnostic indication. See NOTE.

LoBAT

On

The CPU battery is low and needs replacement.

FORCE

On

One or more function block output values have been forced.

RUN

On

Controller is in RUN mode.

Blinking

Controller is in OFFLINE mode

Off

Controller is in PROGRAM mode.

OR

If POWER LED is blinking a fault has been detected in
controller. See NOTE.

NOTE: See Table 20 for the details of the indications and their meaning.