Specifications
Design

98

UMC800 Controller Installation and User Guide

Release F

4/01

Parameter

Description

System Interconnections

Operator Interface (DISPLAY)

Maximum Distance Between Controller File and Operator Interface: 50 feet
Cable Type: 15 conductor, shielded
Cable termination: 15-pin “D” connector at the controller end; removable screw type
terminal strip at operator interface end.

Operator Interface power (24 Vdc) is supplied through the interface cable/connectors.

PC Configurator (CONFIGURATION)

Maximum Distance Between Controller File and PC Configurator: 50 feet
Cable Type: Standard 9-pin RS232, Null Modem
Cable termination: 9-pin “D” connector male (Controller is fitted with female)

Dimensions

Inches: 13.25 wide x 11.87 high x 6 deep
Millimeters: 333.5 wide x 229.2 high x 152.4 deep

Mounting

Surface mounting with four screws in back of chassis
Optional mounting brackets are available.

Safety Protection

Compliant with UL 1092 (draft)/UL 916 Process Control Equipment, CSA, C22.2
No.1010-1 Standard. (24Vdc/ac power certification pending.)

CE Conformity (Europe)

This product is in conformity with the protection requirements of the following
European Council Directives: 73/23/EEC, Low Voltage Directive and 89/336/EEC,
EMC Directive. Conformity of this product with any other “CE Mark” Directive(s) shall
not be assumed.

Product Classification:

Class I: Fixed, Permanently Connected, Industrial Control Equipment with protective
earthing (grounding). (EN 61010-1)

Enclosure Rating:

Controller

Open Equipment: IP00. This Multiloop Process Controller must
be panel mounted within an enclosure (TYPE 1 minimum)
installed in indoor non-hazardous locations.

Operator Interface

Accessory Equipment: The operator interface may be surface
mounted (IP20, TYPE 2) or panel mounted (IP54, TYPE 12) in
indoor non-hazardous locations.

Installation Category
(Overvoltage Category):

Category II: energy-consuming equipment supplied from the fixed installation. Local
level appliances, and industrial control equipment. (EN 61010-1)

Pollution Degree:

Pollution degree 2: Normally non-conductive pollution with occasional conductivity
caused by condensation. (ref. IEC 664-1)

EMC Classification:

Group 1, Class A, ISM Equipment (EN 55011, emissions), Industrial Equipment (EN
50082-2, immunity)

Relay / Alarm Outputs:

Resistive Load: 2 amps @ 240 Vac