Honeywell UMC800 User Manual
Page 35
Mounting and Wiring
Signal Wiring
Release F
UMC800 Controller Installation and User Guide
27
4/01
Analog outputs (module ID 2)
The Analog Output (AO) module provides four outputs at 0 mA to 20 mA (configurable for 4 mA to
20 mA or any span between 0 mA to 20 mA). When not used for an analog output, an output channel may
be used to power a transmitter with 24 Vdc power. The controller will support up to 4 AO modules, for a
total of 16 outputs. Figure 15 shows the terminal connections for the AO module. See Specifications
section for details on all I/O module specifications.
Gnd
4 to 20 ma
Generator
+
-
4 to 20 mA Output
Ground Terminal
Load
Field Wiring
+
-
24 V
DC
Power
Gnd
Field Wiring
12
11
10
9
8
7
6
5
4
3
2
1
2
Channel 4
Channel 3
Channel 2
Channel 1
ATTENTION
Channels not used as analog outputs can be used to supply a transmitter with 24 Vdc power.
Figure 15 AO module terminal block connections