Honeywell UMC800 User Manual
Page 104

Specifications
I/O Module Configuration
96
UMC800 Controller Installation and User Guide
Release F
4/01
Component
Parameter
Description
Pulse/Frequency Inputs
with Digital Outputs
Input 1 to 4
Voltage Levels
Logic Input High Vih:
3.0 Vdc
Logic Input Low Vil:
1.0 Vdc
Absolute Max:
27 Vdc
Absolute Min:
0.0 Vdc
Digital Output
(Open Collector
Circuit)
Max On DC Impedance: 330 ohms
Min Off DC Impedance:
>10 Mohms
Max Source Voltage:
27 Vdc
Min Load DC Impedance: 0 ohms
Frequency Mode
Limitations
Frequency Min:
10 Hz frequency mode
Frequency Max:
100 kHz frequency mode
Min Frequency Duty Cycle @ 100 kHz:
10 %
Max Frequency Duty Cycle @ 100 kHz:
90 %
Pulse Mode Limitations
Pulse Width Min:
100 uSec
Pulse Width Max:
unlimited
Outputs per Module
6
Relay (Alarm) Outputs
(Module ID 6)
Contact Rating
4 A, 250 Vac on resistive load
Contact Type
SPST normally closed (NC), individually configurable to
normally open (NO) via jumper
Time Resolution
4 msec.
Module
Any Digital Output may be configured.
Time Proportional
Outputs (TPO)
Synchronization
Individual TPOs are not synchronized with others.
*Base Power Required is the power required to provided module operation within specifications.