Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06

24

5. Install Firestops
For Horizontal Runs -
Firestops are REQUIRED on both

sides of a combustible wall through which the vent passes.
NOTE: Model DVP-TRAP does not need an exterior

firestop on an exterior combustible wall.
To install firestops for horizontal runs that pass through

either interior or exterior walls:
• Cut a 10-inch by 12-inch (254mm x 305mm) hole through

the wall.

NOTE: The center of the hole is one (1) inch (25.4mm)

above the center of the horizontal vent pipe.

• Position the firestops on both sides of the hole previ-

ously cut and secure the firestops with nails or screws.

• The heat shields of the firestops

MUST BE placed to-

wards the top of the hole.

• Continue the vent run through the firestops.

Figure 23. 10" x 12" Hole and Vent Pipe

Figure 24. Heat Shield, Interior & Exterior Firestops

TRIM HEAT

SHIELD IF TOO

LONG, ADD TO

SHIELD IF TOO

SHORT

EXTERIOR

FIRESTOP

INTERIOR

FIRESTOP

HEAT SHIELD

NOTE: There must be NO INSULATION or other

combustibles inside the framed firestop opening.

10"

12"

INTERIOR

WALL SHIELD

For Vertical Runs - One ceiling firestop is REQUIRED at

the hole in each ceiling through which the vent passes.
To install firestops for vertical runs that pass through ceilings:
• Position a plumb bob directly over the center of the verti-

cal vent component.

• Mark the ceiling to establish the centerpoint of the vent.
• Drill a hole or drive a nail through this centerpoint.
• Check the floor above for any obstructions, such as wir-

ing or plumbing runs.

• Reposition the fireplace and vent system, if necessary,

to accommodate the ceiling joists and/or obstructions.

• Cut an 10-inch x 10-inch (254mm x 254mm) hole through

the ceiling, using the centerpoint previously marked.

• Frame the hole with framing lumber the same size as the

ceiling joists.

If the area above the ceiling is

NOT an attic, position and

secure the ceiling firestop on the ceiling side of the previously

cut and framed hole.

Figure 25. 10" x 10" Hole & New Framing Members

CEILING

NEW

FRAMING

MEMBERS

EXISTING CEILING

JOISTS

CHIMNEY

HOLE

10" (254mm)

10" (254mm)