C. Mantel and Wall Projections

WARNING! Risk of Fire! Comply with all minimum clear-
ances to combustibles as specifi ed. Framing closer than the
minimums listed must be constructed entirely of noncom-
bustible materials (i.e., steel studs, concrete board, etc.)

Note: For non-combustible fi replace fi nish material (marble,
stone, etc) specifi cations refer to Figure 13.10 and Figure 13.11.

Combustible Mantels

Figure 13.4 Combustible Mantel Leg or Wall Projections

(Acceptable on both sides of opening)

Combustible Mantel Legs Or Wall Projections
Extending Past The Face Of The Fireplace

UNLIMITED

6 IN.
MIN.

2 IN.
MIN.

FIREPLACE

OPENING

4 IN.

MAX.

= ACCEPTABLE

NON-COMBUSTIBLE

MANTEL LEG

ZONE

MEASUREMENTS FROM

TOP EDGE OF THE OPENING

7

8

9

10

11

12

13

31

TO CEILING

9

10

11

12

8

7

6

25

18

Note: For non-combustible fi replace fi nish material (marble,
stone, etc) specifi cations refer to Section 13.

Note: All
measurements
in inches.

Non-Combustible Mantels

MEASUREMENTS FROM TOP EDGE OF THE

FIRESCREEN DOOR ASSEMBLY

8

9

10

16

7

6

5

4

1

2

3

4

5

6

12

31

MAX.

MIN.

TO CEILING

1/2

Note: All
measurements
in inches.

Figure 13.2 Minimum Vertical and Maximum Horizontal

Dimensions of Combustibles

Figure 13.3 Minimum Vertical and Maximum Horizontal

Dimensions of Non-Combustibles